4
111 6187 050 E
A 14
Mounting orientation:
It is recommended that the valves be mounted
upright in an easily accessible location. When
mounted horizontally, the yoke should be fitted
such that the stanchions are positioned vertically,
one above the other
For the flow direction the following is valid:
Valve plug close-off movement must always be
directed against flow. This requirement is fulfilled
if the valve is installed in arrow-direction. (See
symbols on valve body)
Two-way
PDTC
E
Equal-linear
-
Linear-equal
Mixing
Diverting
E
L
L
E
Bild_021
Close-off pressures:
Valve series
Stroke
Nominal size / kvs
Close-off pressure (kPa)
VG8000N, PN 16
DN 100/160, DN 125/250, DN 150/350
740, 460, 280
VG8000H, PN 25
DN 100/160, DN 125/250, DN 150/350
740, 450, 270
VBD, PN25
42 mm
DN 80/100
DN 100/160
DN 125/250
DN 150/360
950
570
330
210
Caution:
The heating system should only be pressurised when the valve is fully open!
Device code:
FA-33
- 7 4 1
Voltage supply / frequency
1 =
230V, 50Hz
5 =
24V, 60Hz
6 =
24V, 50Hz
Accessories
00 =
None
01 =
Limit switch
02 =
2 k
Ω
feedback potentiometer
03 =
Limit switch and 2 k
Ω
feedback potentiometer
04 =
135
Ω
feedback potentiometer
40 =
*0-10V pcb
41 =
*0-10V pcb, E
Ring nut wrench
(order No.: 111 6235 010)