background image

Installation, Operation and Maintenance Manual : 036-1011(0806)

Page 19

If the compressors have satisfied their   minimum   run   
times, the compressors and condenser fans are 
de-energized. Otherwise, the unit operates each cooling 
system until the minimum run times for the compressors 
have been completed. Upon the final compressor 
de-energizing, the blower is stopped following the elapse of 
the fan off delay for cooling.

To be available, a compressor must not be locked out due to a 
high or low pressure switch or freezestat trip and the anti short 
cycle delay (ASCD) must have elapsed.

COOLING OPERATION ERRORS

 

Each cooling system is monitored for operation outside of the 
intended parameters. Errors are handled as described 
below. All system errors override minimum run times for 
compressors.

HIGH PRESSURE LIMIT SWITCH

 

During cooling operation, if a high pressure limit switch 
opens, the UCB will de-energize the associated compressor, 
initiate the ASCD (anti short cycle delay), and, if the other 
compressors are idle, stop the condenser fans. If the call for 
cooling is still present at the conclusion of the ASCD, the 
UCB will re-energize the halted compressors.

Should a high pressure switch open three times within two 
hours of operation, the UCB will lock out the associated 
compressors and flash a code (see Table 11). If the other 
compressors are inactive, the condenser fans will be 
de-energized.

LOW PRESSURE LIMIT SWITCH 

The low pressure limit switch is not monitored during the 
initial 30 seconds of a cooling system’s operation. For the 
following 30 seconds, the UCB will monitor the low pressure 
switch to ensure it closes. If the low pressure switch fails to 
close after the 30 second monitoring phase, the UCB will 
de-energize the associated compressor, initiate the ASCD, 
and, if the other compressors are idle, stop the condenser 
fans.

Once the low pressure switch has been proven (closed 
during the 30 second monitor period described above), the 
UCB will monitor the low pressure limit switch for any 
openings. If the low pressure switch opens for greater than 5 
seconds, the UCB will de-energize the associated 
compressor, initiate the ASCD, and, if the other compressor 
is idle, stop the condenser fans. If the call for cooling is still 
present at the conclusion of the ASCD, the UCB will 
re-energize the halted compressor. Should a low pressure 
switch open three times within one hour of operation, the 
UCB will lock out the associated compressor and flash a 
code (Table 11). If the other compressor is inactive, the 
condenser fans will be de-energized.

FREEZESTAT

 

During cooling operation, if a freezestat opens, the UCB will  
de-energize the associated compressor, initiate the ASCD, 

and, if the other compressor is idle, stop the condenser fans. 
If the call for cooling is still present at the conclusion of the 
ASCD, the UCB will reenergize the halted compressor. 
Should a freezestat open three times within two hours of 
operation, the UCB will lock out the associated compressor 
and flash a code (Table 11). If the other compressor is 
inactive, the condenser fans will be de-energized.

LOW AMBIENT COOLING (OPTIONAL)

 

To determine when to operate in low ambient mode, the UCB 
has a pair of terminals connected to a temperature activated 
switch set at 50°F. When the low ambient switch is closed 
and the thermostat is calling for cooling, the UCB will operate 
in the low ambient mode.

Low ambient mode operates the compressors in this 
manner: 10 minutes on, 5 minutes off. The indoor blower is 
operated throughout the cycle. The 5 minute off period is 
necessary to defrost the indoor coil. Low ambient mode 
always begins with compressor operation. Compressor 
minimum run time may extend the minutes of compressor 
operation.

The defrost cycle will begin immediately following the elapse 
of the minimum run time. When operating in low ambient 
mode, the UCB will not lockout the compressors due to a 
freezestat trip. However, a freezestat trip will de-energize the 
associated compressor. If the call for cooling is still present at 
the end of the ASCD and the freezestat has closed, the unit 
will resume operation.

SAFETY CONTROLS

The unit control board monitors the following inputs for each 
cooling system :

1.  A suction line freezestat to protect against low 

evaporator temperatures due to a low air flow or a low 
Installation, return air temperature, (opens at 26 ± 5°F 
and resets at 38 ± 5°F).

2.  A high pressure switch to protect against excessive 

discharge pressures due to a blocked condenser coil or 
a condenser motor failure, (opens at 415 ± 15 psig and 
resets at 280 ± 15 psig).

3. 

 A low pressure switch to protect against loss of 

refrigerant charge, (opens at 35 ± 5 psig and resets at 60 
± 5 psig). The above pressure switches are hard 
soldered to the unit. The refrigeration systems are 
independently monitored and controlled. On any fault, 
only the associated system will be affected by any safety 
/ preventive action.

 

The other refrigerant system will continue in operation 
unless it is affected by the fault as well. The unit control 
board monitors the temperature limit switch of electric 
heat units.

COMPRESSOR PROTECTION

 

The compressors also have inherent (internal) protection. If 
there is an abnormal  temperature  rise  in a compressor, the 

Summary of Contents for DMS 360 Series

Page 1: ...Installation Operation and Maintenance Manual 036 1011 0806 Page 27 NOTES ...

Page 2: ...Installation Operation Maintenance Manual IOM 036 1011 0806 60 Hz ...

Page 3: ...imit switch 19 Freezestat 19 Low ambient cooling 19 Safety controls 19 Compressor protection 19 Flash codes 20 Reset 20 Electric heating sequence of operations 20 Heating operation errors 20 START UP Restart check list 20 Operating instructions 20 Post start check list 20 Shut down 21 Belt drive blower 21 TROUBLE SHOOTING Cooling trouble shooting guide 21 Unit flash codes 25 MAINTENANCE Every mont...

Page 4: ...hing cloth and have a fire extinguisher available for all brazing operations INSPECTION As soon as a unit is received it should be inspected for possible damage during transit If damage is evident the extent of the damage should be noted on the carrier s freight bill RENEWAL PARTS Refer to York USER S MAINTENANCE and SERVICE INFORMATION MANUAL It is strongly suggested that only genuine YORK Spare ...

Page 5: ...available to the consumer and with instructions to retain them for future reference LIMITATIONS These units must be installed in accordance with the applicable national and local safety codes Refer to Unit Application Data table If components are to be added to a unit to meet local codes they are to be installed at the dealer s and or the customer s expense Size of unit for proposed installation s...

Page 6: ...provisions for adequate ventilation air in accordance with applicable provisions of the local building codes Refer to Dimensions and Clearances Refer Figure 8 for the clearances required for servicing and proper unit operation DUCTWORK A closed return duct system should be used This should not preclude use of outdoor fresh air intake The supply and return air duct connections at the unit should be...

Page 7: ...e threads Install a condensate drain line from the one inch FPT female connection on the unit to an open drain NOTE The condensate drain operates in a negative pressure in the cabinet The condensate drain line MUST be trapped to provide proper drainage See Figure 4 FIGURE 4 RECOMMENDED DRAIN PIPING FIGURE 5 LOADING POINTS FIGURE 3 FIXED OUTDOOR AIR DAMPER ...

Page 8: ...tings and ready for operation the tabulated rating with a short circuit capacity of 10K or more for the unit The switch must be separate from all other circuits Wire entry at knockout openings require conduit fittings to comply with local codes Refer to the Dimensions and Clearances Figure 7 for installation location If any of the wire supplied with the unit must be replaced replacement wire must ...

Page 9: ... units are properly phased at the factory Check for proper compressor rotation If the blower or compressors rotate in the wrong direction at start up the electrical connection to the unit is mis phased Change the incoming line connection phasing to obtain proper rotation Scroll compressors operate in only one direction If the scroll is drawing low amperage has similar suction and discharge pressur...

Page 10: ...Installation Operation and Maintenance Manual 036 1011 0806 Page 9 PRODUCT DATA TABLE 4 PRODUCT DATA ...

Page 11: ...Installation Operation and Maintenance Manual 036 1011 0806 Page 10 DIMENSIONS AND CLEARANCES FIGURE 7 DIMENSIONAL DATA AND CLEARANCES ...

Page 12: ...Installation Operation and Maintenance Manual 036 1011 0806 Page 11 DRIVE AND PULLEY DATA TABLE 5 DRIVE AND PULLEY DATA ELECTRICAL DATA TABLE 6 ELECTRICAL DATA ...

Page 13: ...Installation Operation and Maintenance Manual 036 1011 0806 Page 12 ELECTRICAL DATA TABLE 6 ELECTRICAL DATA ...

Page 14: ...Installation Operation and Maintenance Manual 036 1011 0806 Page 13 TABLE 7 FAN PERFORMANCE DATA ...

Page 15: ...anual 036 1011 0806 Page 14 ADDITIONAL PRESSURE DROPS FIGURE 8 PRESSURE DROPS DUE TO OPTIONS The additional pressure losses should be calculated from the graph and ADDED along with the ESP External Static Pressure to calculate fan performance ...

Page 16: ...ta Table 5 WARNING FAILURE TO PROPERLY ADJUST THE TOTAL SYSTEM AIR QUANTITY CAN RESULT IN EXTENSIVE BLOWER DAMAGE SAFETY This section of the IOM covers Safety Aspects applicable to the York DMS Saber Roof Top Air Conditioners Adherence to the instructions detailed hereunder will ensure the safety of the operators prevent damage to the equipment and prevent accidents FIGURE 10 UNIT NAMEPLATE TERMIN...

Page 17: ...gs and signs regarding the units must be absolutely observed STAFF TRAINING The unit should be started up and serviced routine and corrective maintenance by authorized and trained staff only This staff must be informed about possible hazards regarding Electrical connections Piping connections Duct connections Start up These operations must be executed only by trained persons who on behalf of the u...

Page 18: ... Page 17 personnel of the commonly recognized dangers associated with this equipment In addition to following the manufacturer s installation instructions care must be taken to ensure compliance with federal state and local rules regulations codes and standards ...

Page 19: ... completion of a call for cooling Heating always takes priority COOLING SEQUENCE OF OPERATION CONTINUOUS BLOWER By setting the room thermostat fan switch to ON the supply air blower will operate continuously INTERMITTENT BLOWER With the room thermostat fan switch set to AUTO and the system switch set to either the AUTO or HEAT settings the blower is energized whenever a cooling or heating operatio...

Page 20: ...ctive the condenser fans will be de energized FREEZESTAT During cooling operation if a freezestat opens the UCB will de energize the associated compressor initiate the ASCD and if the other compressor is idle stop the condenser fans If the call for cooling is still present at the conclusion of the ASCD the UCB will reenergize the halted compressor Should a freezestat open three times within two ho...

Page 21: ...le 11 SAFETY CONTROLS The unit control board monitors the temperature limit switch of electric heat units The control circuit includes the following safety controls Temperature Limit Switch AUTO This control is located inside the heater compartment and is set to open at 120 F It resets automatically The limit switch operates when a high temperature condition caused by inadequate supply air flow oc...

Page 22: ...l any thermostat calls and set the fan switch to AUTO Wait for the internal overload to reset Test again when cool 5 If blower contactor is not pulled in check for 24 volts at the contactor coil If 24 volts are present but it is not pulled in replace the contactor 6 Failing the above if there is line voltage supplied at contactor and it is pulled in and the supply air blower motor still does not o...

Page 23: ...room thermostat fan switch is in the AUTO position 1 Compressor 2 will not energize simultaneously with compressor 1 if a call for both stages of cooling is received The UCB delays compressor 2 by 30 seconds to prevent a power surge If after the delay compressor 2 does not energize on a second stage call for cooling check for line voltage at the compressor contactor 2 and that the contactor is pul...

Page 24: ...oom thermostat and the UCB Loose wiring from the room thermostat to the UCB 7 If 24 volts is present at the UCB Y3 terminal the compressor may be out due to an open high pressure switch low pressure switch or freezestat Check for 24 volts at the HPS3 LPS3 and FS3 terminals of the UCB If a switch has opened there should be a voltage potential between the UCB terminals e g if LPS3 has opened there w...

Page 25: ...g and in low ambient conditions These options are not enabled by default Local distributors can test the UCB for this programming 11 If none of the above corrected the error test the integrity of the UCB disconnect the C4 terminal wire and the jumper it to the Y4 terminal DO NOT jump the Y4 to C4 terminals If the compressor engages the UCB has faulted 12 If none of the above correct the error repl...

Page 26: ...minal wire and jumper it to the Y1 terminal DO NOT jump the Y1 to C1 terminals If the compressor engages has faulted 13 If none of the above correct the error replace the UCB TABLE 11 UNIT FLASH CODES UNIT FLASH CODES Various flash codes are utilized by the unit control board UCB to aid in troubleshooting Flash codes are distinguished by the short on and off cycle used approximately 200 ms on and ...

Page 27: ... 10 mm to 13 mm when pressed lightly with a finger Every Six Months In addition to the maintenance done every three months The condenser coils should be cleaned by spraying water over it at low pressure or with a brush while ensuring that the fins are not damaged Check all electrical connections and tighten them if required Clean all accessible electrical panels of dirt and dust Before cleaning th...

Page 28: ... has a wide range of product choices for residential and light commercial applications Our offering includes package split air conditioners and heat pumps In addition York offers chillers air handling units ventilation equipment and controls for larger projects Our Cutting Edge Technology is leading the way in developing efficient and environment friendly solutions for your homes offices and place...

Reviews: