background image

689103-BIM-B-1012

8

Johnson Controls Unitary Products

COOLING OPERATION

During cooling operation, the control will receive thermostat signals at
the Y and O input terminals. The control will energize the M compressor
output terminal. This signal energizes the coil of the compressor con-
tactor causing the compressor to run. The control also delivers power to
the COND FAN terminals causing the outdoor fan to operate. The con-
trol energizes the REV VALVE terminal with 24VAC to switch the
reversing valve.

HEATING OPERATION

During normal heating mode, the control will receive a thermostat signal
at the Y input terminal. The control will energize the M compressor out-
put terminal. This signal energizes the coil of the compressor contactor
causing the compressor to run. The control also delivers power to the
COND FAN terminals causing the outdoor fan to operate. The reversing
valve is not energized in heating mode.

EMERGENCY HEAT

When the thermostat calls for emergency heat operation (W signal with-
out a Y signal), the control will de-energize the compressor and ener-
gize the W1/66 terminal immediately.

PRESSURE SWITCH FAULT & LOCKOUT

The heat pump is equipped with a pressure switch and an optional low
pressure switch that are connected to the control at the pressure switch
terminals. If the pressure switch input opens for more than 40 millisec-
onds, the control will de-energize the compressor. If the pressure switch
closes and a thermostat call for compressor operation is present, the
control will apply the five-minute anti-short cycle delay timer and start
the compressor when the timer expires.

When the compressor is started following a pressure switch fault, the
control will start a six-hour timer based on accumulated compressor run
time. If the control senses another opening of the pressure switch
before the timer expires, it will cause a soft lockout condition. The sec-
ond opening of the pressure switch must be greater than 160 millisec-
onds for the lockout to occur. If the second opening is between 40 and
160 milliseconds, the control will de-energize the compressor but not
cause a soft lockout condition. If the control does not sense a second
pressure switch opening before the six-hour timer expires, the timer and
counter will be reset.

During the soft lockout mode, the control will de-energize the compres-
sor and energize the X/L output with the appropriate flash code.

The control will reset the soft lockout condition when any of the follow-
ing occur following removal of the fault condition.

1. Power is cycled to the R or Y inputs of the control. This will cause

the soft lockout condition to be reset when the thermostat is satis-
fied or when the thermostat is set to SYSTEM OFF and back to
HEAT or COOL mode.

2. The TEST terminals are shorted for more than two seconds.

When the soft lockout condition is reset, the control will stop displaying
the fault code and will respond to thermostat inputs normally. 

 FIGURE 10:  

Defrost Operation Curves

REGION C

TERMINATE CURVE

INHIBIT CURVE

INITIA

TE

CUR

VE

REGION A

REGION B

REGION D

REGION E

AMBIENT TEMPERATURE

LIQUID

LINE

(COIL)

TEMPERA

TURE

Defrost prevented from starting

No call for defrost

Time Defrost (6 hour) prevented

No call for Defrost

Time Defrost (6 hour) allowed

Call for Defrost

Defrost Terminated

Summary of Contents for CHJD FLEX SERIES

Page 1: ...ntly hazardous situation which if not avoided will result in death or serious injury WARNING indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury It is also used to alert against unsafe practices and hazards involving only property dam ...

Page 2: ...in the pre determined location 2 Remove the shipping carton and inspect for possible damage 3 Compressor tie down bolts should remain tightened 4 Position the unit on the base provided LIQUID LINE FILTER DRIER The heat pumps have a solid core bi flow filter drier located on the liquid line AIR TEMPERATURE AT OUTDOOR COIL F AIR TEMPERATURE AT INDOOR COIL F Min Max Min Max DB Cool DB Heat DB Cool DB...

Page 3: ...susceptible to kinking and damage 3 Forming Copper for copper tubing only a No attempt should be made to bend the suction line in a shorter radius than 12 See Figure 2 4 How to dispose of excess tubing a Tubing may be longer than required Coil excess tubing nearer the indoor coil rather than the outdoor unit b Excess tubing must be coiled horizontally so the flow of refriger ant is from top to bot...

Page 4: ...ut d Then tighten an additional 1 6 turn to complete the knife edge seal 10 Check for leaks a After the line set connections have been made they should be checked for leaks b If the valves were kept clean and lubricated per instruction no leaks should be found c Use leak detect solution or soap solution for leak testing An elec tronic leak detector is recommended REFRIGERANT LINE SUPPORT Refrigera...

Page 5: ... wiring to be in accordance with national electrical codes NEC and or local city codes 5 Mount the thermostat about 5 feet above the floor where it will be exposed to normal room air circulation Do not place it on an outside wall or where it is exposed to the radiant effect from exposed glass or appliances drafts from outside doors or supply air grilles 6 Route the 24 volt control wiring NEC Class...

Page 6: ...OST OPERATION General The control maintains proper airflow through the outdoor coil during heating operation by melting frost and ice that may form on the coil Frost may accumulate unevenly in different sections of the coil because of the arrangement of the refrigeration circuit within the coil The control may initiate a defrost cycle even when the coil is not completely cov ered with frost This i...

Page 7: ...defrost cycle is necessary The control will initiate a defrost cycle when the liquid line temperature is below the initiate point for the measured ambient temperature See Figure 10 continuously for 4 1 2 minutes This delay eliminates unnec essary defrost cycles caused by refrigeration surges such as those that occur at the start of a heating cycle The control will initiate a defrost cycle every 6 ...

Page 8: ...t cycle delay timer and start the compressor when the timer expires When the compressor is started following a pressure switch fault the control will start a six hour timer based on accumulated compressor run time If the control senses another opening of the pressure switch before the timer expires it will cause a soft lockout condition The sec ond opening of the pressure switch must be greater th...

Page 9: ...rcuit Clean as often as necessary to keep the unit clean Use a brush vacuum cleaner attachment or other suit able means 2 The outdoor fan motor is permanently lubricated and does not require periodic oiling 3 If the coil needs to be cleaned it should be washed with Calgon Coilclean mix one part Coilclean to seven parts water Allow solu tion to remain on coil for 30 minutes before rinsing with clea...

Page 10: ...ce Published in U S A 689103 BIM B 1012 Copyright 2012 by Johnson Controls Inc All rights reserved Supersedes 689103 BIM A 0412 York International Corp 3110 N Mead Wichita KS 67219 SECTION VII WIRING DIAGRAM FIGURE 12 Wiring Diagram ...

Reviews: