689103-BIM-B-1012
Johnson Controls Unitary Products
5
When recovering refrigerant from a system, with a burnout, follow a
safe procedure due to possible contamination.
Contaminated refrigerant must be recovered and returned to the local
refrigeration supply house for proper disposition.
SECTION IV: ELECTRICAL CONNECTIONS
GENERAL INFORMATION & GROUNDING
Check the electrical supply to be sure that it meets the values specified
on the unit nameplate and wiring label.
Power wiring, control (low voltage) wiring, disconnect switches and over
current protection must be supplied by the installer. Wire size should be
sized per NEC requirements.
The complete connection diagram and schematic wiring label is located
on the inside surface of the unit service access panel.
FIELD CONNECTIONS POWER WIRING
1. Install the proper size weatherproof disconnect switch outdoors and
within sight of the unit.
2. Remove the screws from the control box cover and remove from
unit.
3. Run power wiring from the disconnect switch to the unit.
4. Route wires from disconnect through power wiring opening provided
and into the unit control box as shown in Figure 7.
5. Install the proper size time-delay fuses or circuit breaker, and make
the power supply connections.
FIELD CONNECTIONS CONTROL WIRING
1. Route low voltage wiring into bottom of control box as shown in Fig-
ure 7. Make low voltage wiring connections inside the low voltage
box per Figure 8.
2. The complete connection diagram and schematic wiring label is
located on the inside surface of the unit service access panel.
3. Replace the control box cover removed in Step 2.
4. All field wiring to be in accordance with national electrical codes
(NEC) and/or local-city codes.
5. Mount the thermostat about 5 feet above the floor, where it will be
exposed to normal room air circulation. Do not place it on an outside
wall or where it is exposed to the radiant effect from exposed glass
or appliances, drafts from outside doors or supply air grilles.
6. Route the 24-volt control wiring (NEC Class 2) from the outdoor unit
to the indoor unit and thermostat.
DO NOT vent refrigerant to the outdoors.
Avoid getting the refrigerant in the eyes or on the skin.
All field wiring must USE COPPER CONDUCTORS ONLY and be in
accordance with Local, National, Fire, Safety & Electrical Codes.
This unit must be grounded with a separate ground wire in accor-
dance with the above codes.
FIGURE 7:
Outdoor Unit Control Box
To eliminate erratic operation, seal the hole in the wall at the thermo-
stat with permagum or equivalent to prevent air drafts affecting the
operation of in the thermostat.
A Start Assist Kit is available and recommended for long line set
applications or in areas of known low voltage problems.
Start
Relay
(Optional)
Defrost
Control
Board
Start Capacitor
(Optional)
Ground
Lug
“Fingered”
Bushing
Low
Voltage
Box
Reversible High
Voltage Conduit Plate
Contactor
Dual
Run/Fan
Capacitor
NOTICE
NOTICE
FIGURE 8:
Typical Wiring with Thermostat and Furnace / Air Handler
Y
O
R
L
X
W2
G
Y
O
R
X/L
C
W
YEL
ORG
RED
PUR
BLK
BRN
WHT
WALL
THERMOSTAT
YEL (NOT USED)
YEL (NOT USED)
MANUFACTURED HOUSING
ELECTRIC FURNACE
WITH 4 WIRE CONTROL BOX
TYPICAL MANUFACTURED HOUSING INSTALLATION
W / SINGLE STAGE OUTDOOR THERMOSTAT 3024-6881/D
E
G
R
C
W
WHT
GRN
WHT
BLK
RED
+
2
4
5
1
2
+ Confirm that wire is connected
to terminal 2, not terminal 5.
If not, then move wire from
terminal 5 to terminal 2.
W1/66
SINGLE-STAGE OUTDOOR THERMOSTAT
HEAT
PUMP