background image

CD-W00-x0-2 Series Wall Mount CO

2

 and Temperature Transmitters Installation Instructions

4

3. Insert the locking screw on the top of the 

transmitter and secure the locking screw with a 
#1 Phillips-Head screwdriver. 

If power is supplied to the screw terminals, the 
transmitter starts when you close the cover.

Setup and Adjustments

Commissioning

CD-W00-x0-2 Series Wall Mount CO

2

 and 

Temperature Transmitters come from the factory 
calibrated for the following:

output signal (0 to 10 V and 4 to 20 mA) 
proportional to CO

2

 concentration (0 to 2,000 parts 

per million [ppm])

altitude range of 0 to 2,000 ft (0 to 600 m) without 
compensation

For altitudes above 2,000 ft (600 m) where optimum 
accuracy of the CO

2

 concentration measurement is 

essential, modify the Building Automation System 
(BAS) controller’s analog input (AI) high range to 
compensate for sensor placement at other than the 
standard calibration altitude.

To do this, reset the 2,000 ppm value using the 
controller’s compensation factor (CF) shown in 
Figure 7 or Figure 8.

Calculate the corrected value: 

Corrected Value = CF x 2,000

For example, if the sensor is situated at an altitude of 
3,000 ft (914.4 m) above sea level, the CF is 1.10 (see 
Figure 7 or Figure 8). The corrected value is:

Corrected Value = (1.10)(2,000 ppm) = 2,200 ppm

Note:

For altitude compensation, only adjust the AI 

high range. The AI low range should remain at zero. 

CF

Altitude (Feet)

1.30

1.25

1.20

1.15

1.10

1.05

1.00

0.95

0.90

1,000

2,000

3,000

4,000

5,000

6,000

7,000

0

F

IG

:a

lt

co

m

p

_

ft

Figure 7: Altitude Compensation, Feet above Sea Level

CF

0            200            400           600           800         1,000        1,200        1,400         1,600        1,800         2,000       2,200 

Altitude (Meters)

1.15

1.10

1.05

1.00

0.95

0.90

1.20

1.25

1.30

F

IG

:a

lt

c

o

m

p

_

m

Figure 8: Altitude Compensation, Meters above Sea Level

Summary of Contents for CD-W00-00-2

Page 1: ... injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the transmitter IMPORTANT Le CD W00 x0 2 Series Wall Mount CO2 and Temperature Transmitters es...

Page 2: ...ircuited or improperly connected wires may result in permanent damage to the equipment MISE EN GARDE Risque de dégâts matériels Ne pas mettre le système sous tension avant d avoir vérifié tous les raccords de câblage Des fils formant un court circuit ou connectés de façon incorrecte risquent d endommager irrémédiablement l équipement CAUTION Risk of Property Damage Do not run low voltage cable in ...

Page 3: ...ve rectifier we recommend using a DC supply to avoid excessive current peaks Connections to a 24 VAC Power Supply Connecting more than one transmitter to a single 24 VAC transformer forms a common loop and increases the risk of a short circuit We recommend that you use a separate floating supply for each transmitter see Figure 5 If several transmitters share a common transformer always connect the...

Page 4: ...n System BAS controller s analog input AI high range to compensate for sensor placement at other than the standard calibration altitude To do this reset the 2 000 ppm value using the controller s compensation factor CF shown in Figure 7 or Figure 8 Calculate the corrected value Corrected Value CF x 2 000 For example if the sensor is situated at an altitude of 3 000 ft 914 4 m above sea level the C...

Page 5: ...t 21 C Operating Temperature Range 32 to 122 F 0 to 50 C Storage Temperature Range 40 to 158 F 40 to 70 C Operating Humidity Range 0 to 95 RH noncondensing 86 F 30 C maximum dew point Transmitter CO2 Output Signal 4 to 20 mA and 0 to 10 VDC Maximum Output Current 21 mA Maximum Output Voltage 11 V Resolution of Analog Outputs 0 3 ppm CO2 Recommended External Load Minimum 1 000 ohms load resistance ...

Page 6: ...ht Dieser Sensor Transmitter kann nur wandmontiert eingesetzt werden Der elektrische Anschluß ist nach den örtlichen Vorschriften durch autorisiertes Personal durchzuführen Versorgungsspannung und Niederspannung sind getrennt zuzuführen Bei Verwendung von flexiblen Leitungen sind Kabelschuhe zu verwenden Überprüfen Sie alle Kabelverbindungen bevor Sie den Antrieb einschalten Der Kontakt mit Kompon...

Page 7: ...rollera alla kabelförbindelser innan du tillkopplar ställdonet Kontakt med komponenter med farlig spänning kan ge elektriska stötar som kan orsaka allvarliga eller livshotande personskador Kortslutna eller felaktigt anslutna kablar kan resultera i varaktiga skador på utrustningen Om innehållet i den här bruksanvisningen inte efterföljs kan det leda till skada på person eller utrustning Om anslutni...

Page 8: ...кранирован Экран следует заземлять в одной точке на стороне контроллера Сохраните этот документ Portuguese Certifique se que a fonte de alimentação é compatível com a fonte de alimentação especificada na secção de Especificação Técnica Este sensor transmissor foi projetado para montagem somente em parede Toda a fiação eletrica devera ser realizadas segundo a disposicão locais e apenas por pessoal ...

Reviews: