CD-W00-x0-2 Series Wall Mount CO
2
and Temperature Transmitters Installation Instructions
5
Troubleshooting
The CO
2
transmitter is not field repairable. In the event
the unit is not functioning properly, identify the
symptoms and determine a solution:
1. Verify that the unit is mounted properly.
2. Verify that all wiring is correct.
3. Verify that the power supply voltage level is
20 to 30 VAC or 18 to 30 VDC.
If the CO
2
transmitter does not operate after
completing these steps, replace the unit.
Repair Information
If the CD-W00-x0-2 Series Wall Mount CO
2
and
Temperature Transmitters fail to operate within their
specifications, replace the units. For a replacement
CO
2
transmitter, contact the nearest
Johnson Controls® representative.
Technical Specifications
CD-W00-x0-2 Series Wall Mount CO
2
and Temperature Transmitters
CO
2
Measuring Range
0 to 2,000 ppm CO
2
CO
2
Accuracy Across Temperature
Range
68 to 86°F (20 to 30°C): ±(30 ppm +3%
of reading)
50 to 68°F (10 to 20°C), 86 to 104°F (30 to 40°C): ±(35 ppm +3.7% of reading)
32 to 50 °F (0 to 10°C), 104 to 122°F (40 to 50°C): ±(40 ppm +4.8% of reading)
Long-Term Stability
±(15 ppm +2% of reading) over 5 years
Response Time (0 to 63%)
1 minute
Platinum Temperature Sensor
Temperature Sensor: 1,000 ohm, Class F0.15 IEC60751 (Class A), thin-film
platinum
Temperature Coefficient: Approximately 2 ohms per F° (3.9 ohms per C°)
Reference Resistance: 1,000 ohms at 32°F (0°C)
Accuracy: ±0.34F° at 70°F (±0.18C° at 21°C)
Operating Temperature Range
32 to 122°F (0 to 50°C)
Storage Temperature Range
-40 to 158°F (-40 to 70°C)
Operating Humidity Range
0 to 95% RH (noncondensing), 86°F (30°C) maximum dew point
Transmitter CO
2
Output Signal
4 to 20 mA and 0 to 10 VDC
Maximum Output Current: 21 mA; Maximum Output Voltage: 11 V
Resolution of Analog Outputs
0.3 ppm CO
2
Recommended External Load
Minimum 1,000 ohms load resistance for 0 to 10 V
Maximum 600 ohm load resistance for 4 to 20 mA
Power Supply Range
24 VAC ±20%, 50/60 Hz (18 to 30 VDC), Class 2
Power Consumption
<1.0W Average, excluding current output consumption
Current Consumption
100 mA Peak on AC power; 45 mA Peak on DC power
Warm-Up Time
<1 minute
<10 minutes for full specification
Dimensions (H x W x D)
5 x 3-3/16 x 1-1/32 in. (127 x 81 x 26 mm)
Shipping Weight
0.25 lb (114 g)
Compliance
United States
UL Listed, File E107041,
CCN PAZX, UL 916,
Energy Management Equipment,
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Europe
CE Mark - Johnson Controls, Inc. declares that this product is in compliance with
the essential requirements and other relevant provisions of the EMC directive.
Canada
UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205-12, Energy
Management Equipment, Industry Canada Compliant, ICES-003
Australia and
New Zealand
RCM Mark, Australia/NZ Emissions Compliant.
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.