THERMOMETERS (Not Supplied)

Thermometers should be obtained and field installed.
Thermometers  are installed in the system as a means of detecting 

the temperature of the outlet water supply.

This Water Heater has been design certified as complying with 

ANSI Z21.10.3-CSA 4.3 current edition for water heaters and is 

considered suitable for:
Water  (Potable)  Heating  and  Space  Heating: All  models  are 

considered suitable for water (potable) heating and space heating.  
HOTTER WATER CAN SCALD: 
Water heaters are intended to produce hot water. Water heated to a 

temperature which will satisfy space heating, clothes washing, dish 

washing, and other sanitizing needs can scald and permanently injure 

you upon contact. Some people are more likely to be permanently 

injured by hot water than others. These include the elderly, children, 

the infirm, or physically/mentally handicapped. If anyone using hot 

water in your home fits into one of these groups or if there is a local 

code requiring a certain temperature water at the hot water tap, then 

you must take special precautions. In addition to using the lowest 

possible  temperature  setting  that  satisfies  your  hot  water  needs, 

a means such as a *Mixing Valve should be used at the hot water 

taps used by these people or at the water heater. Mixing valves are 

available at plumbing supply or hardware stores. Consult a qualified 

installer  or  service  agency.  Follow  mixing  valve  manufacturer’s 

instructions for installation of valves. Before changing the factory 

setting on the thermostat, read the “Temperature Regulation” section 

in this manual, see Figures 17 and 18.

FACTS TO CONSIDER ABOUT THE LOCATION

Carefully  choose  an  indoor  location  for  the  new  water  heater, 

because  the  placement  is  a  very  important  consideration  for 

the  safety  of  the  occupants  in  the  building  and  for  the  most 

economical  use  of  the  water  heater.  This  water  heater  is  not 

for use in manufactured (mobile) homes or outdoor installation.
Whether replacing an old water heater or putting the water heater 

in a new location, the following critical points must be observed:
1.  Select a location indoors as close as practical to the gas vent or 

chimney to which the water heater vent is going to be connected, 

and as centralized with the water piping system as possible.  

2.  Selected  location  must  provide  adequate  clearances  for 

servicing and proper operation of the water heater.

Installation of water heater must be accomplished in such a manner that 

if the tank or any connections should leak, flow will not cause damage to 

the structure. For this reason, it is not advisable to install water heater 

in an attic or upper floor. When such locations cannot be avoided, a 

suitable metal drain pan should be installed under the water heater. 

Metal Drain pans are available at your local hardware store. Such a 

metal drain pan must have a minimum length and width of at least 

2” (51 mm) greater than water heater dimensions and must be piped 

to an adequate drain. The pan must not restrict combustion air flow.  
Water heater life depends upon water quality, water pressure and the 

environment in which the water heater is installed. Water heaters are 

sometimes installed in locations where leakage may result in property 

damage, even with the use of a drain pan piped to a drain. However, 

unanticipated damage can be reduced or prevented by a leak detector 

or water shut-off device used in conjunction with a piped drain pan. 

These devices are available from some plumbing supply wholesalers 

and retailers, and detect and react to leakage in various ways:

•  Sensors mounted in the drain pan that trigger an alarm or turn off 

the incoming water to the water heater when leakage is detected.

•  Sensors mounted in the drain pan that turn off the water supply 

to the entire home when water is detected in the drain pan.

•  Water supply shut-off devices that activate based on the water 

pressure differential between the cold water and hot water pipes 

connected to the water heater.

•  Devices that will turn off the gas supply to a gas water heater 

while at the same time shutting off its water supply

.

INSTALLATIONS IN AREAS WHERE FLAMMABLE LIQUIDS 

(VAPORS) ARE LIKELY TO BE PRESENT OR STORED (GARAGES, 

STORAGE AND UTILITY AREAS, ETC.): Flammable liquids (such as 

gasoline, solvents, propane [LP or butane, etc.] and other substances 

such as adhesives, etc.) emit flammable vapors which can be ignited by 

a gas water heater’s pilot light or main burner.  The resulting flashback 

and fire can cause death or serious burns to anyone in the area, as well 

as property damage. If installation in such areas is your only option, then 

installation must be accomplished in a way that the pilot flame and main 

burner flame are elevated from floor at least 18 inches. While this may 

reduce chances of flammable vapors, from a floor spill being ignited, 

gasoline and other flammable substances should never be stored or 

Summary of Contents for JW375T75N-AV

Page 1: ...ructions and safety messages could result in death or serious injury This manual must remain with the water heater 599 Hill Street West Fergus ON Canada N1M 2X1 Low Lead Content WARNING If the informa...

Page 2: ...Heater 12 Air Requirements 12 Unconfined Space 13 Confined Space 13 Fresh Air Openings for Confined Spaces 13 Outdoor Air Through Two Openings 13 Outdoor Air Through One Opening 13 Outdoor Air Throug...

Page 3: ...ifornia to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical known to the State of Califor...

Page 4: ...4 GENERAL SAFETY INFORMATION...

Page 5: ...nd then the entire manual carefully If you don t follow the safety rules the water heater will not operate properly It could cause DEATH SERIOUS BODILY INJURY AND OR PROPERTY DAMAGE This manual contai...

Page 6: ...1 1 4 3 2 1 NPT 1 2 NPT 11 15 16 30 3 RECOVERY RATINGS Models Input Approx Gal Cap Approx Liter Cap Temp Rise C 17 22 28 33 39 44 50 56 61 67 72 78 Rating Btu Hr Rating kW F 30 40 50 60 70 80 90 100 1...

Page 7: ...cing and proper operation of the water heater Installation of water heater must be accomplished in such a manner that if the tank or any connections should leak flow will not cause damage to the struc...

Page 8: ...sult in improper and inefficient operation of the water heater producing carbon monoxide gas in excess of the safe limits This could result in serious injury or death Contact your local gas supplier f...

Page 9: ...ertain it does not sag thereby obstructing the combustion air flow HARD WATER Where hard water conditions exist water softening or the threshold type of water treatment is recommended This will protec...

Page 10: ...to manufacturer s specifications If a positive lock up regulator is required follow these instructions 1 Positive lock up gas pressure regulators must be rated at or above the input Btu hr rating of...

Page 11: ...y sized thermal expansion tank must be installed on all closed systems to control the harmful effects of thermal expansion Contact a local plumbing service technician to have a thermal expansion tank...

Page 12: ...ature Pressure Relief Valve discharge line and 2 the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot If after manually operating th...

Page 13: ...eater and the risk of fire or explosion may result It can also create a risk of asphyxiation LOUVERS AND GRILLES Thefreeareasofthefreshairopeningsintheinstructionsthatfollowdonot takeintoaccountthepre...

Page 14: ...e provided with two permanent vertical ducts one commencing within 12 inches 300 mm of the top and one commencing within 12 inches 300 mm of the bottom of the enclosure The vertical ducts shall commun...

Page 15: ...ter heater unless it is vented to the outdoors and has adequate air supply to avoid risks of improper operation explosion or asphyxiation For proper draft hood attachment the draft hood legs may be an...

Page 16: ...IN INCHES MAXIMUM CAPACITY OF PIPE IN CUBIC FEET PER HOUR LENGTH IN FEET NOMINAL IRON PIPE SIZES INCHES INPUT IN THOUSANDS BTU HR 1 2 3 4 1 1 1 4 1 1 2 2 2 1 2 3 4 10 175 360 680 1400 2100 3960 6300 1...

Page 17: ...allation shown in the Figures 15 and 16 Contaminants in the gas lines may cause improper operation of the gas control valve that may result in fire or explosion Before attaching the gas line be sure t...

Page 18: ...18...

Page 19: ...ian or gas supplier If the pilot will not stay lit after several tries turn the gas control knob to OFF Figure A and call your service technician or gas supplier 9 Replace inner and outer burner doors...

Page 20: ...g valves are available at plumbing supply or hardware stores see Figure 2 Follow manufacturer s instructions for installation of the valves Before changing the factory setting on the thermostat read t...

Page 21: ...s of combustion and water vapor SMOKE ODOR It is not uncommon to experience a small amount of smoke and odor during the initial start up This is due to burning off of oil from metal parts and will dis...

Page 22: ...f the flue and vent system may occur if air for combustion contains certain chemical vapors Spray can propellants cleaning solvents refrigerator and air conditioner refrigerants swimming pool chemical...

Page 23: ...sult in overheating and excessive tank pressure Can cause serious injury or death HOUSEKEEPING Fire and Explosion Hazard Do not obstruct combustion air openings at the bottom of the water heater Do no...

Page 24: ...RAGE TANK 1 Turn off the electrical supply to the water heater 2 Ensure the cold water inlet valve is open 3 Open a nearby hot water faucet and let the water run until the water is no longer hot Then...

Page 25: ...ch can condense on the cooler surfaces of the tank Droplets form and drip onto the burner or run on the floor This is common at the time of start up after installation and when incoming water is cold...

Page 26: ...mbly and or thermocouple Defective Gas Control Replace Gas Control PILOT OUTAGE Dirty pilot burner Clean pilot assembly Thermocouple malfunction Replace pilot assembly and or thermocouple Defective Ga...

Page 27: ...s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control SINGLE FLUE 1 UNIT LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSU...

Page 28: ...mostat should be set 5 degrees F higher than the Tank Temperature Control SINGLE FLUE 1 UNIT WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP...

Page 29: ...ermostat should be set 5 degrees F higher than the Tank Temperature Control SINGLE FLUE 1 UNIT WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING P...

Page 30: ...set 5 degrees F higher than the Tank Temperature Control SINGLE FLUE 1 UNIT WITH MIXING VALVE TWO TEMPERATURE LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPE...

Page 31: ...ating thermostat should be set 5 degrees F higher than the Tank Temperature Control SINGLE FLUE 2 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE...

Page 32: ...er than the Tank Temperature Control SINGLE FLUE 2 UNITS TWO TEMPERATURE ONE PRE HEATER ONE BOOSTER HEATER LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERAT...

Page 33: ...33 NOTES...

Page 34: ...34 NOTES...

Page 35: ...d by improper gas supply line sizing gas type venting connections combustion air voltage wiring or fusing Failure to follow applicable codes Failure to follow printed instructions Abuse misuse acciden...

Page 36: ...rights reserved 599 Hill Street West Fergus ON Canada N1M 2X1 Should you have any questions please Email us at techsupport gsw wh com or Visit our website www johnwoodwaterheaters com or Call our Tech...

Reviews: