17
Figure 11.
Electrical connections of heater (JM20E, JM25E, JM30E) and control unit C90
Abbildung 11 Elektroanschlüsse des Saunaofens (JM20E, JM25E, JM30E) und des Steuergerätes C90
Figure 12.
Installation of the control unit on a wall
Abbildung 12. Installation des Steuergerätes an der Wand
Figure 13.
Installation of the sensor
of C90 control unit
Abbildung 13. Installation des Fühlers
des Steuergerätes C90
3.5.1. Installation of the C90 control unit and
sensors (JM20E, JM25E, JM30E)
Install the control unit in a dry place outside the
sauna room at the height of about 170 cm. The
control unit may not be embedded into the wall.
See fig. 13. The control unit includes detailed
instructions for fastening the centre on the wall.
Install the temperature sensor on the wall of the
sauna room above the heater. It should be installed
on the lateral centre line of the heater, 100 mm
downwards from the ceiling. See fig. 14.
3.5.1. Anschluß des C90 Steuergerätes und der
Fühler (JM20E, JM25E, JM30E)
Das Steuergerät wird in einem trockenen Raum
außerhalb der Saunakabine in etwa 170 cm
Höhe angebracht. Das Steuergerät darf nicht in
Wandkonstruktion eingelassen werden. Siehe Abb.
13. In Verbindung mit dem Steuergerät werden
genauere Anweisungen zu dessen Befestigung an
der Wand gegeben.
Der Temperaturfühler wird an der Saunawand
oberhalb des Saunaofens, 100 mm unterhalb
der Decke auf der Achse in Breitenrichtung des
Saunaofens angebracht. Siehe Abb. 14.