5.
After the fan starts, adjust speed knob to get the appropriate speed and
best effect
Shut-down:
1.
Stop device by turning the power switch from RUN to position STOP.
IMPORTANT NOTE
:
Power outage is prohibited during the fan normal operation.
In case of a power failure and reversion, the Eurus HVLS ceiling fan system starts
automatically as the power knob is still at RUN position. To prevent motor
damage, ensure that the power switch is turned to STOP position in the event of
a power failure.
Maintenance
NOTE
Risk of fire, electric shock, or injury to persons during cleaning, servicing and user
maintenance. Disconnect the fan system from the power supply before servicing.
Preventive Maintenance
Our product design is maintenance-free, but in order to ensure the long life of the
normal operation, the fan should also be maintained regularly, especially when
applied in harsh environments.
➢
All fan hardware should be periodically checked and tightened with the
appropriate torque values.
➢
Check safety cable and guy cables for fraying or damage.
➢
Remove dust from fan blades and motor every six months.
➢
Ensure the fan is not exposed to direct contact with water or sunlight.
Interval The maintenance content
Test run Check the operation of the fan, any abnormal sound or vibration
2500h
Clean the dust on the inverter
Clean the dust on the blades
5000h Check the mechanical fasteners to ensure that there's no looseness
Check wire cable to ensure that there's no damage
NOTES
If the fan is running with a serious abnormal noise or vibration, it indicates that
some damages to the mechanical parts exist somewhere, you should
immediately shut down the fan and do a comprehensive inspection.
For any fan or inverter controller maintenance, please be sure that the fan stops
running and cut off the controller power to protect the safety of personnel.