2.2 FIREPLACE INSTALLATION 

2.2.1 Reinforcing Location-Supporting Frame & Load Bearing Support/ Chimney Connector: 

1. Before beginning the installation, consult Table 1 for weights of supporting frame, Load Bearing 
Support/Chimney Connector, total weight of chimney, smoke pipe, fireplace & components.  
2. Determine the exact location of the supporting frame and the Load Bearing Support/Chimney 
Connector above the ceiling in accordance with the proposed location of the ceiling-suspended 
fireplace so that the fireplace will be perfectly centered in the room below with the lower shelf of the 
fireplace 650mm (26 5/8’’) above the finished floor when the installation is completed.  
3. Multiply by two the total weight of all suspended components, including the weight of the 
supporting frame and Load Bearing Support/Chimney Connector, the chimney, smoke pipe and the 
fireplace to achieve a minimum 200% structural safety factor when reinforcing the structure around 
the proposed location of the supporting frame and Load Bearing Support/ Chimney Connector.  

TABLE 1: WEIGHTS CEILING-SUSPENDED TATIANA 997CFO FIREPLACES (Approx.)                       
(with e.g. ASHT SECURE-TEMP +  10’’ Chimney - 25mm (1’’) wall thickness)                                                                                                           
(Height of installation floor to ceiling: Min. 2.43m (8’) 

Weight of 
fireplace 

 

Load Bearing 
Support & 
Supporting 
frame

 

length of smoke 
pipe & weight of 
smoke pipe

 

Length of chimney & 
weight (13.35 kg/m -  
26.7 lbs/yd. – 8.9 lbs/ft) 

 

Approximate  Total 
weight of installed 
fireplace 

115 kg             
(253 lbs) 

 
56.5 kg (124 lbs)

 

0-2.43m(8’) Min. 
height installation, 
no smoke pipe 

4.6m to 4.9m   (15’ to 17’) 
Max. 68.8 kg (151 lbs) 

240.3kg ( 529 lbs) 

115 kg             
(253 lbs) 

 
56.5 kg (124 lbs)

 

750mm(29.5’’) 
50.3 kg (110 lbs) 

10m (33’)  
133.5 kg (294 lbs) 

355.3 kg (782 lbs) 

115 kg             
(253 lbs) 

 
56.5 kg (124 lbs)

 

4m. inside height 
install. Pipe 1.56m 
(61.5’’)long 
104 kg (230 lbs) 

15m (50’) 
202.3 kg (445 lbs) 

 
477.8kg (1051 lbs) 

2.2.2  INSTALLATION OF HEARTH EXTENSION: 

1. Remove all combustible floor coverings, e.g. carpeting, linoleum, etc., from the area under where 
the fireplace is to be suspended. 
2. Centered on the planned location of the fireplace, install, flush with the finished floor, a round 
hearth extension of a minimum diameter of 1.996m ( 78 19/32’’) and at least 9.5 mm (3/8’’) thick                    
( backed by a sheet metal plate if over a combustible structure) and made of approved non-
combustible material such as ceramic tiles, stone, masonry or concrete, flush with the floor. This 
conforms to applicable standards and is permitted since the bottom of the firebox opening is raised 
at least 203 mm ( 8’’) above the top of the hearth extension.  

 

2.2.3  Installation Smoke Pipe and Fireplace on Load Bearing Support

/Chimney 

Connector

1. Make sure that the structure has been sufficiently reinforced as detailed in 2.2.1.  Install the 
supporting frame and Load Bearing Support/Chimney Connector above the ceiling making sure that 
it is properly situated and aligned so that when the installation is completed the fireplace will be 
centered on the room below.  Install the trim ring around the Load Bearing Support. 
2. For added height, install the required length(s) of smoke pipe onto the Load Bearing Support. 
3. Before installing the fireplace on the smoke pipe, remove all possible internal components of the 
fireplace to lighten it during installation. 

Page 5 

 

Summary of Contents for Tatiana 997CFO

Page 1: ...I de Lh rat 63310 RANDAN FRANCE This appliance is The manufacturer may update this manual from time to time and cannot be responsible for problems injuries or damages arising out of the use or misuse...

Page 2: ...or serious injuries and or important material damages WARNING Do not use materials other than those provided by the manufacturer for use during the installation as they may be safety hazards and their...

Page 3: ...d weather preheat the chimney flue to prevent smoke flow reversal Hold a lighted rolled up newspaper inside the fireplace towards the smoke pipe for a few minutes 6 Only use the grate made by JC Borde...

Page 4: ...ANSI Z 223 1 NFPA 54 2 THE FIREPLACE 2 1 INTRODUCTION The TATIANA 997 CFO fireplace is an energy efficient heat generating fireplace It will provide you with a lifetime of comfort and enjoyment provi...

Page 5: ...e pipe 4 6m to 4 9m 15 to 17 Max 68 8 kg 151 lbs 240 3kg 529 lbs 115 kg 253 lbs 56 5 kg 124 lbs 750mm 29 5 50 3 kg 110 lbs 10m 33 133 5 kg 294 lbs 355 3 kg 782 lbs 115 kg 253 lbs 56 5 kg 124 lbs 4m in...

Page 6: ...ace Warning For centrally located fireplaces a minimum clearance to combustibles of 1 2m 48 must be maintained 360 o around the fireplace For single wall smoke pipe a minimum clearance to combustibles...

Page 7: ...Page 7...

Page 8: ...Page 8...

Page 9: ...Vent Secure Temp ASHT 254mm 10 Ext Dia 305mm 12 Projet Nova Temp TM HT6103 254mm 10 Ext Dia 305mm 12 Dura Tech DTC 254mm 10 Ext Dia 305mm 12 10 chimneys approved to UL 103HT Standard USA installations...

Page 10: ...2 2 5 Typical Approved Installation of an Offset in Smoke Pipe 2 2 6 Installation of Anti Sway Bracket Page 10...

Page 11: ...e to the firescreen Do not overfire this fireplace Max 11kg 24 lbs of firewood as it may overheat causing a hazard permanent damage to the fireplace or in the presence of creosote even igniting a chim...

Page 12: ...allow combustion air to flow under the wood for a more efficient burn This will result in less creosoting greater efficiency and a longer lasting fire 2 3 6 Combustion Air As is common with open firep...

Page 13: ...insulated enclosure around the chimney there might still be draft problems caused by extremely cold weather To correct this it is recommended to preheat the chimney by holding a lit rolled up newspape...

Page 14: ...n soil or otherwise locally dispersed they should be retained in the closed container until all cinders have thoroughly cooled 3 Replace the two piece grate and reinstall the firescreen using two cool...

Page 15: ...TS LIST For TATIANA 997 Centrally Located Fireplace Illustration Part Name Part Number Grate for TATIANA 997 Central Model AGF997CFO Expanded Metal Mesh Firescreen PE997FO Combustion Air Intake Recomm...

Page 16: ...claim Returned products are to be shipped prepaid to the distributor for investigation If the product s is are found to be defective Bordelet Industrie S A S will at their option repair or replace suc...

Page 17: ...ginal purchaser This warranty does not cover cost of removal reinstallation or shipping to repair or replace the defective part s nor administration fees incurred by the original purchaser Bordelet In...

Page 18: ...ualified chimney sweep CAUTION Do not install this fireplace vented gas log combination in a confined space or in tightly constructed house without providing for combustion and ventilation air as stat...

Page 19: ...has been applied to joints around windows and door frames between sole plates floors wall ceiling joints wall panels penetrations for plumbing electrical wires gas lines vents and other openings The N...

Page 20: ...ture or other objects around the fireplace that will obstruct the flow of combustion air Maintain a minimum clearance of 1 2m 48 to all objects around the fireplace Keep the room where the fireplace i...

Page 21: ...on fireplace 6 Center gas fire log set on mounting plate making sure that proper clearance will be maintained from the firescreen to prevent damaging it drill mounting holes and bolt screw on gas fir...

Page 22: ...Typical Vented Gas Log Set Page 22...

Page 23: ...he buyer user as a result of injury or damage to an ultimate user or other person caused by the installation of a vented gas log set in a JC Bordelet S A S fireplace whether the injury or damage resul...

Reviews: