Doc. ref :
333130A-EN
2018/01/05
Page 17 / 44
DRAFT R revision5
Configuring the restart mode of transmitter
RSEF
5.1.6
This function defines the restart mode of safety transmitter (activation of the radio transmission) after a stop caused by deactivation of its
safety input (i.e.: emergency stop button pressed) or cut of its power supply. By default (
“ex-factory"), the transmitter restart mode is
«
Manual
».
«
Manual
» restart mode :
The safety transmitter is manually restarted (radio transmission activated) by pressing on a « Restart » pushbutton
following deactivation and activation of its safety input.
«
Automatic
» restart mode :
The safety transmitter is automatically restarted (radio transmission activated) following deactivation and activation of its
safety input.
IMPORTANT :
Do not connect a restart button in this mode (input nb.17 not connected).
This function is configured using
micro-switch No. 8
1-
Deactivate the safety input of the transmitter
RSEF
(1)
2-
Using
micro-switch No. 8
, select the transmitter restart mode : « Automatic » or « Manual » :
3-
Activate the safety input of the transmitter
RSEF
(2) ; the two indicator lights,
V1
and
V2
, flash alternately to indicate the
system is on standby for validation.
4-
Press the validation button (
BPV
) ; indicator lights
V1
and
V2
go off.
5-
To exit this configuration mode, deactivate, then activate the safety input (1)(2).
(1) If an emergency stop palmswitch is wired on this input, the component must be locked.
(2) If an emergency stop palmswitch is wired on this input, the component must be unlocked.
Wiring diagram with restart button (« manual » restart mode) :
In the event of deactivation followed by activation of the safety input (emergency stop, for example), the transmitter will only be
able to transmit provided the « restart » pushbutton has been pressed.
Note :
If the other setting has also been modified during this procedure (
as “Radio channel number” or “restart mode”), each modified
setting have to be performed one by one.