Page 18
= Peak value
= Minimum value
= Supply
Outputs K1 and K2
The UMG96 has got two outputs. Each output can either be used as a
switching output or pulse output.
The presetting for the outputs is:
Output 1 = Pulse output for real energy
Output 2 = Pulse output for reactive energy
Outputs, which are assigned to a energy, energy as a pulse output.
Outputs, which are assigned to a measured value, energy as a swit-
ching output.
The real energy can only be assigned to output 1 and reactive
energy can only be assigned to output 2.
One measured value can be assigned to each switching output. If
necessary, you can activate each single phase. A switching output
switches, when a set limit is exceeded or underscored.
Therefore it is possible to supervise only the current in L1 and L2
with one threshold, for instance.
The condition of the outputs is marked by a cyclic symbol.
Output K1
PRG
Wh
L1
L2
L3
K1
Output is off, no current flowing.
Output is on, a current can flow.
Output K2
PRG
VArh
L1
L2
L3
K2