background image

www.janitza.de

UMG 604-PRO

12

5. 1 

Three-phase 4-conductor systems

The device can be used in three-phase 
4-conductor systems (TN, TT networks) 
(50 Hz, 60 Hz) with an earthed neutral 
conductor. The bodies of the electrical 
system are earthed.
The voltage between phase and neutral 
conductor may be a maximum of 300 V AC.

The device is only suitable for environments 
in which the permissible measurement 
voltage surge and overvoltage category are 
not exceeded.

UMG604-PRO

Earthing of 
the system

DC

AC/DC

PE

230/400 V 50/60 Hz

L2
L3

N

L1

Auxiliary supply

Voltage measurement

4M

4M

4M

4M

L1

L3

L2

N

4M

L4

N

L1

240V 
50/60Hz

5. 2 

Three-phase 3-conductor systems

The device can be used in non-earthed three-
phase 3-conductor systems (IT network).

The voltage between phase and phase may 
be a maximum of 480 V AC (50 Hz, 60 Hz).
The IT network is not earthed at the neutral 
point of the voltage generator. The bodies of 
the electrical system are earthed. Earthing via 
a high ohm impedance is permitted.

IT networks are only permitted in certain 
systems with their own transformers or 
generators.

230/400 V 50/60 Hz

UMG604-PRO

Earthing of 
the system

DC

AC/DC

L2

L3

N

L1

Auxiliary supply

4M

4M

4M

4M

L1

L3

L2

N

4M

L4

Impedance

Voltage measurement

400 V 50/60 Hz

DC

AC/DC

L2

L3

Auxiliary supply

Voltage measurement

4M

4M

4M

4M

L1

L3

L2

4M

L4

Earthing of 
the system

Impedance

L1

UMG604-PRO

N

Fig. Schematic diagram, UMG 604-PRO in a TN network

Fig. Schematic diagram, UMG 604-PRO in an IT network 
with N

Fig. Schematic diagram, UMG 604-PRO in an IT 
network without N.

Summary of Contents for UMG 604-PRO

Page 1: ...Power Quality Analyser UMG 604 PRO User manual and technical data Part no 33 03 125 Janitza electronics GmbH Vor dem Polst ck 6 D 35633 Lahnau Support tel 49 6441 9642 22 email info janitza com www ja...

Page 2: ...7 4 2 Network failure detection 7 4 3 Usage concept 7 4 4 GridVis network analysis software 7 4 5 Features 8 4 6 Product overview 9 4 7 Installation location 10 5 Network systems 11 5 1 Three phase 4...

Page 3: ...0 Operation 35 10 1 Button functions 35 10 2 Display mode 35 10 3 Programming mode 36 10 4 Display password 36 10 5 Homepage password 36 11 Configuration 37 11 1 Current transformer ratio 37 11 2 Curr...

Page 4: ...y 58 14 Service and maintenance 59 14 1 Repair and calibration 59 14 2 Front film 59 14 3 Disposal 59 14 4 Service 59 14 5 Battery 59 14 6 Firmware update 59 15 Procedure in the event of faults 61 16...

Page 5: ...www janitza de UMG 604 PRO IV 19 Dimension diagrams 77 19 1 Front view 77 19 2 Side view 78 20 Connection example 79 21 Short introduction setting primary current 81...

Page 6: ...es with the installation manual Please read and understand the documents enclosed with the product first Keep the documents enclosed with the product available throughout the entire service life of th...

Page 7: ...www janitza de UMG 604 PRO 2...

Page 8: ...l must be read before using the device must be kept throughout the entire service life of the product and be readily available for reference Follow additional legal and safety regulations required for...

Page 9: ...connecting connections earth the device at the ground wire connection if present Hazardous voltages may be present in all switching parts that are connected to the power supply Hazardous voltages may...

Page 10: ...can be assumed that risk free operation is no longer possible the device must be immediately put out of operation and secured against being put back into operation again It can be assumed that risk f...

Page 11: ...ggable 6 1 89 10 051 Slotted screwdriver 0 40 x 2 mm ESD 1 08 01 505 2m patch cable twisted grey UMG PC switch connection 1 52 00 008 RS485 termination resistor 120 ohms 1 For the item number see the...

Page 12: ...asurement inputs can be configured using the GridVis software The device bridges the following network failures on the auxiliary voltage input Supply voltage 230 V AC Bridging time max 80 ms 4 Product...

Page 13: ...temperature range 10 C to 55 C Measurement Measurement in IT TN and TT networks Continuous sampling of the voltage and current measurement inputs Logging and storing transients 50 s Capture more than...

Page 14: ...Temperature measurement input 3 Hidden service button 4 Profibus interface optional 5 Ethernet interface 6 Current measurement inputs I1 to I4 7 RS485 interface 8 Digital inputs outputs 9 Supply volt...

Page 15: ...ce can be installed in switching cabinets or in small installation distributors in accordance with DIN 43880 It is assembled on a 35 mm mounting rail in accordance with DIN EN 60715 It can be installe...

Page 16: ...or systems with earthed neutral conductor Separated single phase three conductor system with earthed neutral conductor The device can be used in 2 3 and 4 conductor networks TN TT and IT networks dome...

Page 17: ...sed in non earthed three phase 3 conductor systems IT network The voltage between phase and phase may be a maximum of 480 V AC 50 Hz 60 Hz The IT network is not earthed at the neutral point of the vol...

Page 18: ...the device can be used Fig Table of suitable rated voltages in a three phase 4 conductor network Fig Table of suitable rated voltages in a three phase 3 conductor network UL N UL L 66 V 115 V 120 V 20...

Page 19: ...www janitza de UMG 604 PRO 14...

Page 20: ...death can occur due to touching bare or stripped wires that are live device inputs that are dangerous to touch Therefore note the following De energise your system before starting the work The inputs...

Page 21: ...rous if touched Install a disconnector as described in 6 1 Disconnectors c c CAUTION Malfunction due to incorrect connection If the device is connected incorrectly incorrect measured values may be ret...

Page 22: ...the current transformer to the earth You must short circuit the secondary connections on the current transformer before interrupting the power supply If a test switch which automatically short circuit...

Page 23: ...y current 5 A UMG S2 I S1 P1 P2 Einspeisung 1 Supply 1 Einspeisung 2 Supply 2 1P1 1P2 K L k l 1S2 1S1 1S1 1S2 2S1 2S2 2S1 2S2 k l K L 2P1 2P2 Verbraucher A Consumer A Verbraucher B Consumer B Fig Circ...

Page 24: ...es for voltage measurement in Three phase 4 conductor networks and Single phase 3 conductor networks Fig Connection examples for voltage measurement in Three phase 3 conductor networks L3 L2 L1 N L1 L...

Page 25: ...ection variant 0 Fig Current measurement in the single phase 3 conductor system Connection variant 0 Fig Current measurement connection example for connection variant 1 N L3 L2 L1 I1 S1 S2 I2 S1 S2 I3...

Page 26: ...ig Measurement of the voltage between N and PE Measurement of the current in the neutral conductor C C NOTE If the baseline measurement inputs V1 V3 is connected to a three phase 3 conductor network t...

Page 27: ...e to connect to the temperature sensor c c CAUTION Risk of injury due to electric voltage Insufficient insulation of the operating equipment at the temperature measurement input to the mains supply ci...

Page 28: ...ally above the earthing clamp in order to avoid damage due to cable movements Use suitable cable glands to feed the cables into the cabinet for example armoured conduit couplings c c WARNING Risk of i...

Page 29: ...should not be exceeded The permissible ohmic load must be greater than 3 kOhm and the capacitive load caused by the transmission line must be lower than 2500 pF Fig Plug arrangement for the PC connec...

Page 30: ...sistor Device with RS485 interface with termination resistor on the device 7 3 2 Cable type CAT cables are not suitable for bus wiring Instead we recommend the following cable type Unitronic Li2YCY TP...

Page 31: ...nection is switched on must be under current It is recommended that the master be placed at the end of a segment If the master is replaced with a bus connection the bus must be switched off Replacing...

Page 32: ...with termination resistors 7 5 1 Connection of the bus wiring The inbound bus wiring is connected to terminals 1A and 1B The bus wiring for the next device in line is connected to terminals 2A and 2B...

Page 33: ...www janitza de UMG 604 PRO 28...

Page 34: ...o electrical faults If the line is longer than 30 m there is an increased probability of transmission errors and damage to the device due to atmospheric discharge Use a shielded cable for connection t...

Page 35: ...ternal auxiliary voltage of 20 to 28V DC and an external 1 5 kOhm resistor each 1 5k S0 pulse transducer 24V DC Fig UMG 604 PRO with inputs for 24V Example with S0 pulse transducer Fig UMG 604 PRO wit...

Page 36: ...tion of a DC voltage relay to the digital outputs 16 17 Digital Output 1 UMG 604 PRO Digital outputs K2 K1 24V DC 18 Digital Output 2 Fig Connection of an AC voltage relay to the digital outputs 16 17...

Page 37: ...www janitza de UMG 604 PRO 32...

Page 38: ...e current and voltage measurement inputs 9 3 Connecting the measured voltage The device is suitable for measuring voltages of up to 300VAC to earth and 520 V AC phase to phase The device is not suitab...

Page 39: ...e current displayed by the device must correspond to the current input The device must display approx zero amperes in the short circuited current measurement inputs The current transformer ratio is fa...

Page 40: ...sing buttons 1 and 2 The service button is only for use by trained service employees Fig Front view of UMG 604 PRO control element 10 2 Display mode After the power returns the device is in display mo...

Page 41: ...y password Fig Display example for Programming mode address 000 with a content of 5 000 Address Content PRG 10 4 Display password To make it harder to accidentally modify the programming data on the d...

Page 42: ...dresses 010 to 041 deletes the current transformer values in addresses 000 and 001 11 Configuration Address Current transformer values 000 L1 L2 L3 L4 primary 001 L1 L2 L3 L4 secondary 010 L1 primary...

Page 43: ...sformer input You can program voltage transformers with the same voltage transformer ratios in addresses 002 and 003 You can program voltage transformers with different voltage transformer ratios in a...

Page 44: ...0 Modbus RTU slave 3 Debug 6 SLIP for internal use only Address Settings 200 Device address 1 to 255 applies to Modbus and Profibus 1 factory default setting 202 Baud rate RS485 0 9600Bit s 1 19200Bit...

Page 45: ...he device is factory set to the DHCP client m m CAUTION Damage to property due to incorrect network settings Incorrect network settings can cause faults in the IT network Obtain information from your...

Page 46: ...and are available to each interface in the UMG604 2 Big endian high byte before low byte Little endian low byte before high byte 11 8 2 Device master file The device master file abbreviated as the GS...

Page 47: ...ve power L2 Float 1 14 53 Active power L3 Float 1 15 57 Active power L4 Float 1 16 61 Cosphi math L1 Float 1 17 65 Cosphi math L2 Float 1 18 69 Cosphi math L3 Float 1 19 73 Cosphi math L4 Float 1 20 7...

Page 48: ...49 Cosphi math L1 Float 1 14 53 Cosphi math L2 Float 1 15 57 Cosphi math L3 Float 1 16 61 Frequency Float 1 17 65 Total active power L1 L3 Float 1 18 69 Total reactive power L1 L3 Float 1 19 73 Total...

Page 49: ...ctive energy L2 Float 1 13 49 Inductive reactive energy L3 Float 1 1 1 Active power L1 Float 1 2 5 Active power L2 Float 1 3 9 Active power L3 Float 1 4 13 Total active power L1 L3 Float 1 5 17 Curren...

Page 50: ...tal active power L1 L4 Reactive power fundamental oscillation L1 Reactive power fundamental oscillation L2 Reactive power fundamental oscillation L3 Reactive power fundamental oscillation L4 Total rea...

Page 51: ...www janitza de UMG 604 PRO 46...

Page 52: ...onfiguration Via the parameter _MODE_NTP the Modbus address can be found in the Modbus address list of your device at www janitza de 11 10 1 Important Modbus parameters for the PTP configuration of th...

Page 53: ...h a master as the slave and synchronizes its time with the master Boundary clock BC Clock that contains several ordinary clocks several ports and as the master synchronizes several slaves with its tim...

Page 54: ...nge has been exceeded in the current or voltage circuit Fig Measured value indication for the firmware release RxD TxD L1 L2 L3 L4 Input Output Firmware release Fig Measured value indication with time...

Page 55: ...www janitza de UMG 604 PRO 50...

Page 56: ...access the homepage for your device by entering the device s PI address in a web browser on your end device Section 11 7 Ethernet configuration explains how to connect the device to the internet You c...

Page 57: ...display individual measured values The following menu items are available Short overview Detailed measured values Diagrams Events Transients 13 1 1 Short overview The Short overview provides you with...

Page 58: ...asured values In the overview you can call extensive information on the following points Voltage Current Power Harmonic oscillations Energy Peripheral devices digital inputs outputs temperature measur...

Page 59: ...isplay of current and historical measured values with automatic scaling In order to display a graphic of the measured values drag the required values from the list on the left edge of the screen into...

Page 60: ...ic illustration of transients within a date list Transient voltages are fast impulse transient effects in electrical networks are unpredictable from a time perspective and have a limited duration are...

Page 61: ...ommon standards Here you have access to permanent power quality monitoring in accordance with IEC 61000 2 4 in customer supply networks The display is based on the traffic light principle which makes...

Page 62: ...your device retrospectively by installing additional apps 13 3 1 Push Service The push service is an example of an installable app The push service sends measured values directly from the device to a...

Page 63: ...se the Downloads item to access the download area on the Janitza homepage You can download catalogues operation manuals and additional documentation from here 13 4 3 Display The Display item provides...

Page 64: ...answer any questions device name see rating plate serial number see rating plate software release see measured value indication measured voltage and supply voltage precise description of the error 14...

Page 65: ...www janitza de UMG 604 PRO 60...

Page 66: ...rmer Voltage displayed is too high or too low Measurement in the wrong phase Check connection and if necessary correct Voltage transformer incorrectly programmed Read out and program the voltage trans...

Page 67: ...rogram the CT ratio on the current transformer The current circuit is assigned to the wrong voltage circuit Check connection and correct if necessary The programmed voltage transformer ratio is incorr...

Page 68: ...esistance IK08 according to IEC 62262 16 2 Environmental conditions The device is intended for weatherproof fixed installation and meets the operational conditions in accordance with DIN IEC 60721 3 3...

Page 69: ...range Operating range Power consumption Overvoltage category 20 V to 50 V 50 60Hz DC 20 V to 70 V 10 of nominal range max 5 W 8 VA 150 V CATII 16 5 Protection class Protection class II in accordance...

Page 70: ...asic program 200 ms Cable length up to 30 m 32 81 yd unshielded from 30 m 32 81 yd shielded Potential separation and electrical safety for the digital inputs and outputs The digital inputs and outputs...

Page 71: ...fibus interfaces and the digital inputs outputs The external temperature sensor must be double insulated from the system parts that carry voltages that are dangerous to touch per IEC61010 1 2010 1 rng...

Page 72: ...6 A char B approved i a w UL IEC Resolution on the display 10 mA Metering range 0 005 to 7 Amps Crest factor 2 related to 6 Amps Overvoltage category 300 V CAT III Measurement surge voltage 4 kV Power...

Page 73: ...t interfaces have a functional insulation form each other and from RS232 RS485 the temperature measurement input and digital inputs and outputs The interfaces for the devices connected here must have...

Page 74: ...ass 2 DIN EN62053 23 Current transformer 1 A Class 2 DIN EN62053 23 Frequency 0 01 Hz Internal clock 1 minute month 18 C to 28 C The specification applies under the following conditions annual re cali...

Page 75: ...www janitza de UMG 604 PRO 70...

Page 76: ...ormer secondary L1 1 to 400 V 400 020 Current transformer primary L2 0 to 1000000 A 5 021 Current transformer secondary L2 1 to 5 A 5 022 Voltage transformer primary L2 0 to 1000000 V 400 023 Voltage...

Page 77: ...1 0 110 Current transformer switch L1 to L3 0 three current transformers 1 two current transformers Aron circuit 0 to 1 0 111 Voltage measurement network configuration 0 three phase 4 conductor system...

Page 78: ...to 6 0 0 Modbus RTU slave 3 Debug 6 SLIP for internal use only 0 to 6 0 Address Designation Setting range Unit Default 205 DHCP mode 0 static IP 1 BootP 2 DHCP client 0 1 2 2 300 IP address xxx 0 to 2...

Page 79: ...128 130 0 502 Homepage password 0 to 9999 xxxx 510 Enabling EMAX option licence part 1 0 to 9999 xxxx 511 Enabling EMAX option licence part 2 0 to 9999 xxxx 520 Enabling BACnet option licence part 1...

Page 80: ...e energy L4 Active energy L3 Active energy L2 Active energy L1 to L4 Active energy L1 to L3 cos phi L4 cos phi L1 cos phi L3 cos phi L2 cos phi L1 to L3 Voltage L1 N Voltage L2 N Voltage L4 N Voltage...

Page 81: ...www janitza de UMG 604 PRO 76...

Page 82: ...UMG 604 PRO www janitza de 77 19 Dimension diagrams 19 1 Front view Fig Front view of UMG 604 PRO with installation dimensions...

Page 83: ...www janitza de UMG 604 PRO 78 19 2 Side view Fig Schematic side view of UMG 604 PRO with installation dimensions...

Page 84: ...sung Current measurement I1 1 2 3 4 5 6 7 8 I2 I3 I4 9 10 11 12 Spannungsmessung Voltage measurement L1 L2 L3 L4 N 13 Versorgungs spannung Auxiliary Supply Dig I O RS485 RS232 An In Option Option RS48...

Page 85: ...www janitza de UMG 604 PRO 80...

Page 86: ...pressing buttons 1 and 2 simultaneously for approximately one second The symbol for programming mode PRG appears The contents of address 000 are displayed 2 Enter the primary current by using button...

Page 87: ...guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equip...

Reviews: