UMG 604-PRO
12
5. 1
Three-phase 4-conductor systems
The device can be used in three-phase
4-conductor systems (TN, TT networks)
(50 Hz, 60 Hz) with an earthed neutral
conductor. The bodies of the electrical
system are earthed.
The voltage between phase and neutral
conductor may be a maximum of 300 V AC.
The device is only suitable for environments
in which the permissible measurement
voltage surge and overvoltage category are
not exceeded.
UMG604-PRO
Earthing of
the system
DC
AC/DC
PE
230/400 V 50/60 Hz
L2
L3
N
L1
Auxiliary supply
Voltage measurement
4M
4M
4M
4M
L1
L3
L2
N
4M
L4
N
L1
240V
50/60Hz
5. 2
Three-phase 3-conductor systems
The device can be used in non-earthed three-
phase 3-conductor systems (IT network).
The voltage between phase and phase may
be a maximum of 480 V AC (50 Hz, 60 Hz).
The IT network is not earthed at the neutral
point of the voltage generator. The bodies of
the electrical system are earthed. Earthing via
a high ohm impedance is permitted.
IT networks are only permitted in certain
systems with their own transformers or
generators.
230/400 V 50/60 Hz
UMG604-PRO
Earthing of
the system
DC
AC/DC
L2
L3
N
L1
Auxiliary supply
4M
4M
4M
4M
L1
L3
L2
N
4M
L4
Impedance
Voltage measurement
400 V 50/60 Hz
DC
AC/DC
L2
L3
Auxiliary supply
Voltage measurement
4M
4M
4M
4M
L1
L3
L2
4M
L4
Earthing of
the system
Impedance
L1
UMG604-PRO
N
Fig. Schematic diagram, UMG 604-PRO in a TN network
Fig. Schematic diagram, UMG 604-PRO in an IT network
with N
Fig. Schematic diagram, UMG 604-PRO in an IT
network without N.
Summary of Contents for UMG 604-PRO
Page 7: ...www janitza de UMG 604 PRO 2...
Page 19: ...www janitza de UMG 604 PRO 14...
Page 33: ...www janitza de UMG 604 PRO 28...
Page 37: ...www janitza de UMG 604 PRO 32...
Page 51: ...www janitza de UMG 604 PRO 46...
Page 55: ...www janitza de UMG 604 PRO 50...
Page 65: ...www janitza de UMG 604 PRO 60...
Page 75: ...www janitza de UMG 604 PRO 70...
Page 81: ...www janitza de UMG 604 PRO 76...
Page 85: ...www janitza de UMG 604 PRO 80...