www.janitza.de
UMG 604-PRO
8
4. 5
Features
General
• Installation on a 35 mm DIN rail
• LCD display, backlight (optional)
• Operation via 2 buttons
• 4 voltage and 4 current measurement inputs
• 1 temperature measurement input
• 2 digital outputs and 2 digital inputs
• RS485 interface (Modbus RTU, Modbus master)
• RS232 interface
• Profibus DP / V0 (optional)
• Ethernet (web server, e-mail)
• Suitable for installation in installation distributors
• Suitable for measurements in networks with frequency converters
• Working temperature range -10 °C to +55 °C
Measurement
• Measurement in IT, TN and TT networks
• Continuous sampling of the voltage and current measurement inputs
• Logging and storing transients > 50 µs
• Capture more than 800 measured values
• Fourier analysis 1st to 40th Harmonics for U, I, P (consumption/delivery), Q (ind./
capacitive)
• Temperature measurement
• Working measurement, measurement uncertainty:
- Class 0.5 for ../5 A converter
- Class 1 for ../1 A converter
• Programming separate applications in Jasic
C
C
NOTE!
Measurements in medium and
high-voltage networks are always
performed via current and voltage
transformers. Special safety
requirements must be adhered to for
these, which will not be described
in detail here.
Summary of Contents for UMG 604-PRO
Page 7: ...www janitza de UMG 604 PRO 2...
Page 19: ...www janitza de UMG 604 PRO 14...
Page 33: ...www janitza de UMG 604 PRO 28...
Page 37: ...www janitza de UMG 604 PRO 32...
Page 51: ...www janitza de UMG 604 PRO 46...
Page 55: ...www janitza de UMG 604 PRO 50...
Page 65: ...www janitza de UMG 604 PRO 60...
Page 75: ...www janitza de UMG 604 PRO 70...
Page 81: ...www janitza de UMG 604 PRO 76...
Page 85: ...www janitza de UMG 604 PRO 80...