UMG 604-PRO
www.janitza.de
29
8.
Digital inputs and outputs
8. 1
Digital inputs
The device has 2 digital inputs to which you
can connect one signal generator each.
An input signal is detected on a digital input if
a voltage of at least 10 V and maximum 28 V
DC is applied.
The flowing current is at least 1 mA
and a maximum of 6 mA.
Pay attention to the supply voltage's polarity!
c
c
CAUTION!
Transmission errors and
damage to property due to
electrical faults
If the line is longer than 30 m, there is
an increased probability of transmission
errors and damage to the device due to
atmospheric discharge.
Use a shielded cable for connection to
the digital inputs.
c
c
CAUTION!
Damage to property due
to connection errors
Ensure that the supply voltage:
• is DC voltage.
• has the right polarity.
• is not above the maximum permissible
voltage.
+
-
24V
DC
Fig. Connection example of digital inputs.
Fig. Example for the connection of external switch
contacts S1 and S2 to digital inputs 1 and 2.
+
-
S2
S1
24V
=
UMG 604-PRO
Digital inputs 1-2
4.4k
19
Digital
Input 1
3.9V
3.9V
20
21
Digital
Input 2
4.4k
Summary of Contents for UMG 604-PRO
Page 7: ...www janitza de UMG 604 PRO 2...
Page 19: ...www janitza de UMG 604 PRO 14...
Page 33: ...www janitza de UMG 604 PRO 28...
Page 37: ...www janitza de UMG 604 PRO 32...
Page 51: ...www janitza de UMG 604 PRO 46...
Page 55: ...www janitza de UMG 604 PRO 50...
Page 65: ...www janitza de UMG 604 PRO 60...
Page 75: ...www janitza de UMG 604 PRO 70...
Page 81: ...www janitza de UMG 604 PRO 76...
Page 85: ...www janitza de UMG 604 PRO 80...