12
UMG 511
Failure to comply with the minimum
clearances can destroy the UMG511
in higher temperatures!
m
Assembly
Place of Installation
The UMG511 is suitable for installation in fixed,
weather protected switch boards. Conducting
switch boards have to be grounded.
Installation position
In order to achieve sufficient ventilation, the
UMG511 has to be installed vertically. The clea-
rance has to be at least 50mm at the top and bot-
tom and 20mm at the side.
Front Board Cutout
Cutout size:
:
138
+0,8
x 138
+0,8
mm
Fig. installation po-
sition of UMG511;
view from behind.