91
UMG 511
Current measurement
Rated current
5A
Resolution
0.1mA
Measuring range
0.001 .. 7.4A
rms
Crest factor
2.4
Overvoltage category
300V CAT III
Measurement surge voltage
4kV
Power consumption
ca. 0.2 VA (Ri=5 mohm)
Overload for 1 second
120A (sinusoidal)
Scanning frequency
20kHz
Connectable cables (current measurement and voltage measurement)
Only one cable per clamp may be connected!
Single wire, multi-wire, fine wire
0.2 - 2.5mm
2
, AWG 24-12
Pin cable lugs, wire end ferrules
0.25 - 2.5mm
2
Torque
0.5 - 0.6Nm
Strip length
7mm