89
UMG 511
Inputs and outputs
8 digital inputs
- Maximum counting frequency
20Hz
- Reaction time (Jasic programme)
200ms
- Input signal is applied
18V .. 28V DC (typical 4mA)
- Input signal is not applied
0 .. 5V DC, current lower than 0.5mA
5 digital outputs, semi conductor relay, not short-circuited
Switching voltage
max. 60V DC, 30V AC
Switching current
max. 50m A
eff
AC/DC
Reaction time (Jasic programme)
200ms
Issue of voltage dips
20ms
Issue of voltage excesses
20ms
Impulse output (working impulse)
max. 20Hz
Cable length
up to 30m not shielded,
larger than 30m shielded
Connection capacity of clamping points (inputs and outputs)
Rigid/flexible
0.14 - 1.5mm
2
, AWG 28-16
Flexible with wire end ferrules without plastic sleeves
0.25 - 1.5mm
2
Flexible with wire end ferrules with plastic sleeves
0.25 - 0.5mm
2
Torque
0.22 - 0.25Nm
Strip length
7mm