background image

Page 4

Universal Measuring Device UMG 500A

Installation

When installing and mounting the Universal Measuring Device UMG 500A, the VDE Regulation 0113 must be adhered
to. Before connecting up, ensure that the local supply conditions agree with the data given on the nameplate.
The installation facilities must provide a switch or a power switch. The switch must be installed close to the device, easy
to be operated by the user. The switch must be marked as a disconnection device for the UMG 500A.

Auxiliary voltage

Terminals L, N
For auxiliary voltage see nameplate. The auxiliary voltage must be connected via a 2A time-lag auxiliary fuse to the
terminals  “auxiliary voltage” L and N at the rear of the instrument.

Measurement inputs

Terminals L1, L2, L3, 1k-3l
The voltages to be measured, L1, L2 and L3 must be similarly connected via a 2A auxiliary fuse to the terminals L1, L2
and L3.
The currents to be measured must be connected in a like manner to the terminals 1k to 3l. Please note that the continuous
measurement current must not exceed 5A, (1 A for instruments with .../1 A transformers), whether measuring directly
or via a current transformer.

Relay outputs K1 and K2

Terminals 1-3, 4-6
The instrument is equipped with two floating threshold value contacts “min” and “max” which are available as change-
over contacts with terminals 1 to 3 or 4 to 6. If the reading falls below the “min” value programmed for the threshold
function or rises above the “max” value, the appropriate relay is activated. The threshold values “min” and “max” can
be programmed via keystrokes.

Analogue output “0..20 mA”

Terminals 7, 8
The measured values displayed are converted by the UMG into a 0..20 mA analogue signal. The analogue signal can
be tapped at terminals 7 and 8 and passed on, for example, to a recorder. It is possible to connect several instruments
in series, but the total load may not exceed 500 

. The analogue output is scaled with the help of key “0..20 mA”.

Optionally, the device can be provided with  4..20 mA analogue output.

“Clear work” input

Terminals 9, 10
A contact can be connected to terminals 9 and 10 which when closed, erases the real work and reactive work which has
been registered up to this point and restarts the time measurement. Measurement of real and reactive work then
recommences synchronously with the value 0 kWh or 0 kvarh.

“Remote” input

Terminals 11, 12
A switch, key switch or similar can be connected to terminals 11 and 12. When the switch is closed, the instrument cannot
be operated from the keypad, and the LED “remote” at the front of the panel lights up. Unauthorised or inadvertent
operation can thus be prevented.  The contact has no influence on the choice of the measurement function or on the storage
of peak values.

“RS 485” Serial interface

Terminals TxD A,B and RxD A,B
These terminals are required in conjunction with the PC software option for communicating with the computer used. (see
serial interface)

Summary of Contents for UMG 500 A

Page 1: ...Universal Measuring Device UMG 500 A Janitza electronic GmbH Vor dem Polst ck 1 D 35633 Lahnau Tel 0 64 41 9642 0 Fax 0 64 41 9642 30 Doc No 1 010 006 1...

Page 2: ...9 Real power 9 Mean real power 9 Measuring period 9 Remaining time 9 Reactive power 10 Real work 10 Reactive work 10 Frequency 10 Power factor 10 Harmonic wave content of voltage 10 Analogue output 1...

Page 3: ...analogue output threshold contacts serial interface designed for networking Application 1 Peak values of harmonics are stored without date and time Construction features Universal Measuring Device UM...

Page 4: ...1 to 3 or 4 to 6 If the reading falls below the min value programmed for the threshold function or rises above the max value the appropriate relay is activated The threshold values min and max can be...

Page 5: ...onnect current path for L1 4 1 1 Switch on auxiliary voltage measured voltage and measured current 4 1 2 Using the operating keys of the UMG 500A cause the current in L1 to be displayed and compare it...

Page 6: ...99 kV 0 5500 A 0 5500 A 0 9999 kW opt 0 00 99 99 MW 0 9999 kVA opt 0 00 99 99 MVA 0 9999 kvar 0 000 9999 kvarh 255 0 000 9999 kWh 255 48 00 62 00Hz 100 0 0 25 5 L2 L3 Sum 0 9999 kW Peak values L1 0 9...

Page 7: ...by trained staff after a period of about 5 years The batteries have a design life of approx 8 to 10 years Batteries 2 off Lithium batteries voltage 3 V diameter 12 5 mm 2 5 mm thick Panasonic order c...

Page 8: ...measurement function Erasing the accumulated work Restart of averaging power and current Summe sum Selection key sum With this key the sums of the measurement functions real power apparent power reac...

Page 9: ...y service therealpowerisdisplayedwiththreedigitsas Asanoption theinstrumentcandisplaytherealpower in MW to two decimal places P U I Apparent power This function shows the apparent power of the measure...

Page 10: ...ly after erasure If there is a power failure the time measurement will be interrupted Frequency This function displays the frequency of the voltage in L1 The unit of measurement is indicated by the LE...

Page 11: ...al to or bigger than 500 if the maximum pulse frequency of 0 25 Hz should not be exceeded 0 20mA Analogue output Allocation In order to allocate a particular measuring function to the output the desir...

Page 12: ...bed under Peak values but using key 5A instead of the function key for the corresponding measurement value In combination with the keys and the settings can be changed There is no automatic changeover...

Page 13: ...at care must be taken to ensure that the parallel port of the PC 25 pin socket is not used because otherwise damage to the device can occur Alternatively a connecting cable 25 pin socket socket can be...

Page 14: ...ng stations using the master slave principle i e the measuring stations never transmit independently only after being called up by the host system The protocol consists essentially of control characte...

Page 15: ...digit kW kVA cos phi kWh 1 5 digit kvar kvarh 1 5 5 digit Harmonic wave content 10 10 digit Environment Operating temperature 10 C 45 C Storage temperature 20 C 60 C Humidity class F to DIN 40040 15...

Page 16: ...ion switch closed clear work switch open measure serial interface RS 485 analogue output floating threshold contacts auxiliary voltage see nameplate consumer measured voltage see nameplate interface c...

Page 17: ...4 wire switch closed clear work switch open measure serial interface RS 485 analogue output floating threshold contacts interface converter RS 485 RS 232 switch closed remote switch open local consume...

Page 18: ...osed clear work switch open measure serial interface RS 485 analogue output floating threshold contacts interface converter RS 485 RS 232 switch closed remote switch open local auxiliary voltage see n...

Page 19: ...ive ground terminal and is suited for applications in overvoltage category III and contamination level 2 EN 55011 06 1992 RFI product standard Group 1 Class B residential and commercial premises EN 50...

Reviews: