Universal Measuring Device UMG 500A

Primary current of current transformer

When this key is pressed, the programmed state is displayed and can be altered by additionally pressing the
“+” or “-” keys.  Setting range:  1 ... 5000 A in 1 A steps.
The set value is always based on a current transformer secondary current of 5 A (standard).
Example: for a current transformer of 500/5, “500” must be set.
For instruments fitted with  a 1A  transformer secondary (optional), the primary current must be set similarly
Example: for  1000/1 the value is “1000”.

.. / 5A

-

+

Key functions and Programming

Programming of Universal Measuring Device UMG 500A is carried out with the remote/local contact open, using the
keyboard and the digital display. Following a power failure, it is not necessary to reprogram the device, because the
programmed data and peak values are stored.

“+” key

This key is used - partly in conjunction with other keys -  for the following functions:

• Changing set values
• Reading the peak value of the displayed function.
• Indicating overflows of work measurements (W)

“-” key

This key is used - partly in conjunction with other keys -  for the following functions:

• Changing set values
• Erasing the peak value of the displayed measurement function.
• Erasing the accumulated work
• Restart of averaging power and current

Summe

ΣΣΣΣΣ

sum

Selection key “sum”

With this key, the sums of the measurement functions real power, apparent power, reactive power, real work,
reactive work and power factor, from L1, L2 and L3 are displayed. For all measurement functions other than
those referred to, this key is inoperative.

L2

L3

L1

Selection of outer conductor L1, L2 or L3

The outer conductor, for which the associated measurement values are to be displayed, is selected with this
key.  The selected outer conductor is indicated by the LED “L1”, “L2” or “L3”.  The frequency is only
measured in L1.

U

Voltage transformer

If required, the ratio of the voltage transformer used can be set with the aid of this key.  The factor
is displayed with one decimal place.  In combination with the “+” or “-” keys, the displayed value

can be altered. Setting range: 0.1 ... 999.9

Example:

Transformer

Displayed / set value

10,000 V/100 V

100.0

12,000 V/110 V

109.1

.. / 5A

Note

The voltage transformer ratio is set to 1.0 for the standard version.  If this value is wrongly set
by mistake, this will result in the measured voltage and the values derived from it being
incorrectly calculated and displayed!

Note

In case of option ../1 A, primary current may not be set higher than 1000 A, otherwise calculation
of current and other dependent values (power, power factor, work) will be incorrect!

Summary of Contents for UMG 500 A

Page 1: ...Universal Measuring Device UMG 500 A Janitza electronic GmbH Vor dem Polst ck 1 D 35633 Lahnau Tel 0 64 41 9642 0 Fax 0 64 41 9642 30 Doc No 1 010 006 1...

Page 2: ...9 Real power 9 Mean real power 9 Measuring period 9 Remaining time 9 Reactive power 10 Real work 10 Reactive work 10 Frequency 10 Power factor 10 Harmonic wave content of voltage 10 Analogue output 1...

Page 3: ...analogue output threshold contacts serial interface designed for networking Application 1 Peak values of harmonics are stored without date and time Construction features Universal Measuring Device UM...

Page 4: ...1 to 3 or 4 to 6 If the reading falls below the min value programmed for the threshold function or rises above the max value the appropriate relay is activated The threshold values min and max can be...

Page 5: ...onnect current path for L1 4 1 1 Switch on auxiliary voltage measured voltage and measured current 4 1 2 Using the operating keys of the UMG 500A cause the current in L1 to be displayed and compare it...

Page 6: ...99 kV 0 5500 A 0 5500 A 0 9999 kW opt 0 00 99 99 MW 0 9999 kVA opt 0 00 99 99 MVA 0 9999 kvar 0 000 9999 kvarh 255 0 000 9999 kWh 255 48 00 62 00Hz 100 0 0 25 5 L2 L3 Sum 0 9999 kW Peak values L1 0 9...

Page 7: ...by trained staff after a period of about 5 years The batteries have a design life of approx 8 to 10 years Batteries 2 off Lithium batteries voltage 3 V diameter 12 5 mm 2 5 mm thick Panasonic order c...

Page 8: ...measurement function Erasing the accumulated work Restart of averaging power and current Summe sum Selection key sum With this key the sums of the measurement functions real power apparent power reac...

Page 9: ...y service therealpowerisdisplayedwiththreedigitsas Asanoption theinstrumentcandisplaytherealpower in MW to two decimal places P U I Apparent power This function shows the apparent power of the measure...

Page 10: ...ly after erasure If there is a power failure the time measurement will be interrupted Frequency This function displays the frequency of the voltage in L1 The unit of measurement is indicated by the LE...

Page 11: ...al to or bigger than 500 if the maximum pulse frequency of 0 25 Hz should not be exceeded 0 20mA Analogue output Allocation In order to allocate a particular measuring function to the output the desir...

Page 12: ...bed under Peak values but using key 5A instead of the function key for the corresponding measurement value In combination with the keys and the settings can be changed There is no automatic changeover...

Page 13: ...at care must be taken to ensure that the parallel port of the PC 25 pin socket is not used because otherwise damage to the device can occur Alternatively a connecting cable 25 pin socket socket can be...

Page 14: ...ng stations using the master slave principle i e the measuring stations never transmit independently only after being called up by the host system The protocol consists essentially of control characte...

Page 15: ...digit kW kVA cos phi kWh 1 5 digit kvar kvarh 1 5 5 digit Harmonic wave content 10 10 digit Environment Operating temperature 10 C 45 C Storage temperature 20 C 60 C Humidity class F to DIN 40040 15...

Page 16: ...ion switch closed clear work switch open measure serial interface RS 485 analogue output floating threshold contacts auxiliary voltage see nameplate consumer measured voltage see nameplate interface c...

Page 17: ...4 wire switch closed clear work switch open measure serial interface RS 485 analogue output floating threshold contacts interface converter RS 485 RS 232 switch closed remote switch open local consume...

Page 18: ...osed clear work switch open measure serial interface RS 485 analogue output floating threshold contacts interface converter RS 485 RS 232 switch closed remote switch open local auxiliary voltage see n...

Page 19: ...ive ground terminal and is suited for applications in overvoltage category III and contamination level 2 EN 55011 06 1992 RFI product standard Group 1 Class B residential and commercial premises EN 50...

Reviews: