Page 35
Problem
Possible Cause
Corrective Action
“Cell On” indicator does not come on.
Chlorine Production set to 00%.
Adjust CHLORINE PRODUCTION to desired
Percentage.
If No Flow also….
Insufficient water flow. Cell is plugged with debris,
pump has lost prime.
Remove obstruction and/or clean cell. See
Section
6.4, Electrolytic Cell Cleaning
. Prime pump if
necessary.
If No Flow also….
Flow/Temp/Salinity Sensor not plugged in.
Plug in Flow/Temp/Salinity Sensor. See
Section 2,
Figures
2a and 2b.
Salt level below 2.0 gpl.
Add salt as described in
Section 4.7
.
Problem
Possible Cause
Corrective Action
“No Flow” indicator stays on
continuously.
Pump fails to provide sufficient water flow.
Check for correct operation of the pump. Ensure
there is no loss of pump prime or clogged strainer
baskets.
Closed valves.
Check and correct all valve alignments.
Dirty filter.
Follow filter cleaning procedures.
Obstruction in the AquaPure cell.
Remove cell for inspection. Follow cleaning
procedures. See
Section 6.4, Electrolytic Cell
Cleaning
.
Flow/Temp/Salinity Sensor not installed properly.
Ensure that the Flow/Temp/Salinity Sensor is
installed according to
Section 3, Figure 12
. If not,
contact a pool professional.
Flow/Temp/Salinity Sensor not plugged in.
Plug Flow/Temp/Salinity Sensor into connector on
power center printed circuit board. Turn power to
unit off and back on (Cycle Power). See wiring
diagram in Figures 2a and 2b. See also,
Section
6.5, Flow/Temp/Salinity Sensor Cleaning, Step 4
.
Flow/Temp/Salinity Sensor elements covered with PVC
glue, taped over, or covered with other debris.
Remove and clean Flow/Temp/Salinity Sensor.
Wrap Flow /Salinity sensor threads with Teflon tape
and reinstall. See
Sections 3.5 and 6.5
.
Defective Flow/Temp/Salinity Sensor.
Contact your authorized service representative.
Problem
Possible Cause
Corrective Action
Salt level too high.
Too much salt has been added to pool.
Backwash or partially drain pool and dilute with
fresh water until salinity returns to
3.0 gpl to 3.5 gpl.