Page 31
CAUTION
Disable
TEST MODE
after use. Failure to
disable
TEST MODE
after use will allow the
heat pump to bypass the built-in delays, which
could lead to equipment damage
.
NOTE
The
TEST MODE
resets to
DISABLE
(default)
on every power-up.
7.3.6 Load
Defaults
1.
Make sure the control is in the
OFF
mode.
2.
To enter the Service Setup mode, press and hold
the
MENU, POOL
and
SPA
button for 5 seconds.
NOTE
The display will revert back to
OFF
after one
minute since the last key press.
3.
This feature allows for original factory settings
to be restored. To select Load Defaults, use the
Up
or
Down
button to scroll through to display
LOAD DEFAULTS
. Press the
MENU
button. The
NO
(default mode) appears, use the
Up
or
Down
button to scroll to display the desired option, press
the
MENU
button to select
.
Press
POOL
or
SPA
to exit the Service Setup mode.
NOTE
The
LOAD DEFAULTS
resets to
NO
(default)
after
execution.
7.3.7
Coil Temperature Calibration
1.
Make sure the control is in the
OFF
mode.
2.
To enter the Service Setup mode, press and hold
the
MENU, POOL
and
SPA
button for 5 seconds.
NOTE
The display will revert back to
OFF
after one
minute since the last key press.
3.
This feature adjusts the defrost set point. To
select Coil Temperature Calibration, use the
Up
or
Down
button to scroll through to display
COIL TEMP CAL
. Press the
MENU
button. The
2°C (35°F)
(default mode) appears, use the
Up
or
Down
button to scroll to display the desired
temperature adjustment, press the
MENU
button
to select
.
Press
POOL
or
SPA
to exit the Service
Setup mode.
7.3.8
Water Temperature Calibration
1.
Make sure the control is in the
OFF
mode.
2.
To enter the Service Setup mode, press and hold
the
MENU, POOL
and
SPA
button for 5 seconds.
NOTE
The display will revert back to
OFF
after one
minute since the last key press.
3.
This feature adjusts the heat pump water
temperature sensor. To select Water Temperature
Calibration, use the
Up
or
Down
button to scroll
through to display
WATER TEMP CAL
. Press
the
MENU
button. The
0°C
(
0°F)
(default mode)
appears, use the
Up
or
Down
button to scroll to
display the desired temperature adjustment, press
the
MENU
button to select
.
Press
POOL
or
SPA
to exit the Service Setup mode.
7.3.9
Water Temperature Differential
1.
Make sure the control is in the
OFF
mode.
2.
To enter the Service Setup mode, press and hold
the
MENU, POOL
and
SPA
button for 5 seconds.
NOTE
The display will revert back to
OFF
after one
minute since the last key press.
3.
This feature sets the temperature differential the
heat pump will turn back on. To select Water
Temperature Differential, use the
Up
or
Down
button to scroll through to display
WATER TEMP
DIFF
. Press the
MENU
button. The
1°C (1°F)
(default mode) appears, use the
Up
or
Down
button to scroll to display the desired temperature
adjustment, press the
MENU
button to select
.
Press
POOL
or
SPA
to exit the Service Setup
mode.