SPECIFICATIONS
Actuator Inputs
Connections:
Coded screw terminals.
Control Circuit:
Two-wire.
Power Input:
Actuator Outputs
Torque:
See Table-1.
Shaft Rotation:
MA-305, MA-405, MA6-305, MA6-405,
CW 180° when power is applied.
MA-318, MA-41x, MAx-318, MAx-41x,
CW 180° when power is applied.
Spring Return:
CCW to the original position when the actuator is de-energized.
Auxiliary Switch (-500 Models):
SPDT makes (or breaks) the circuit at the powered end of
stroke.
Environment
Ambient Temperature Limits:
Shipping & Storage,
-40 to 136 °F (-40 to 58 °C).
Operating,
-40 to 136 °F (-40 to 58 °C).
Humidity:
5 to 95% RH, non-condensing.
Location:
NEMA Type 4 when used with the gasket (provided) and water-tight conduit
connectors (not provided), optional hazardous location models.
Agency Listings:
US Standard UL 873,
Underwriters Laboratories (File #E9429 XAPX, Temperature
Indicating and Regulating Equipment).
Candadian Standard C22.2 No. 24:
Underwriters Laboratories (File #E429 Category
XAPX7, Temperature Indicating and Regulating Equipment).
Hazardous Location Models,
UL file #E29291. Designed for use in hazardous locations
N.E.C., Class 1, Groups C and D, and Class 2, Groups E, F, and G. Temperature code T6 for
hazardous housing.
Table-1 Model Chart.
Part Number
Power
Supply
Auxiliary
Switch
a
Input
Watts
VA
Rated
Torque
lb-in. (N-m)
No Load
Timing in
Seconds at
75 °F (24 °C)
b
Mounting
Application
Vac
Hz
Running
Holding
MA-305
24
60
No
25
56
56
16 (1.8)
20
Any Position
(Horizontal
Output Shaft
Position
Preferred)
Damper
Actuators
MA-305-500
Yes
MA-405
120
No
48
48
MA-405-500
Yes
MA-318
24
No
70
Running
25
Holding
92
32
60 (6.8)
Output Shaft
Must Be
Horizontal
Damper
and Valve
Actuators
MA-318-500
Yes
MA-416
208
60
No
104
38
MA-416-500
Yes
MA-418
120
No
108
42
MA-418-500
Yes
MA-419
240
No
120
39
MA-419-500
Yes
MA5-419
50
No
MA5-419-500
Yes
a 4.4 FLA, 26.4 LRA @ 24 or 120 Vac; 2.4 FLA, 13.2 LRA @ 240 Vac.
b Spring return timing with full load opposing spring is approximately 60 sec.
45
Summary of Contents for 700E
Page 2: ...SN _______________...
Page 4: ......
Page 6: ......
Page 10: ...3...
Page 30: ...23...
Page 31: ...Figure 3 Oyler Through the Wall Installation with Direct Vent 24...
Page 32: ...25...
Page 33: ...Oyler With Exhaust Hood Vent Unit shown is a Model 700 Left Firebox Figure 5 26...
Page 36: ...29...
Page 38: ...31...
Page 39: ...32...
Page 40: ...33...
Page 41: ...34...
Page 42: ...35...
Page 46: ...39...
Page 47: ...40...
Page 48: ...41...
Page 49: ...42...
Page 50: ...43...
Page 55: ...48...
Page 56: ...49...
Page 60: ......