Danfoss AKS 41 Liquid Level Transmitter 

Publication 9-45 

 

Section 9 

Page 12 of 18 

 

Issue 1 : 10/11 

 

 

 
 

Fig 6 4 to 20 mA Output Signal Damping 

 

Signal damping is factory set at 15 seconds and can be altered within the 
range 1 to 120 seconds.  Setting the signal damping is performed while 
the transmitter is operating. 

(a) 

With the transmitter in operation, press the calibration push-button 
once for each second by which you want to increase the damping. 

Example: 

1 press = 1 second 
2 presses = 2 seconds 

120 presses = 120 seconds 
121 presses = 120 seconds 

(b) 

After the first press the green LED stops ‘flashing’ and now only 
illuminates when the button is pressed.  10 seconds after the last 
press, the new signal damping value is saved in memory and the 
green LED resumes ‘flashing’. 

(c) 

If signal damping is set too high, repeat the procedure. 

Each time damping is set, damping starts at 1 second.  For 
example, to increase the damping from 15 to 25 seconds, this 
cannot be done with 10 presses of the button, it is necessary to 
press the button 25 times. 

6.5. 

Restore Factory Default Settings 

To restore default settings, press the calibration push-button and keep it 
depressed for a minimum of 20 seconds, until the green LED starts 
‘flashing’.  Release the push-button.  When the LED starts flashing, reset 
to factory default settings is completed. 

7. 

Commissioning 

 WARNING 

The pressure and temperature parameters detailed in 
Table 1 must NOT be exceeded when pressure testing 
the plant. 

When the plant is charged with refrigerant for the first time, leave the 
isolating stop valves in the open position.  If the level column has been 
isolated for maintenance while the vessel to which it is fitted is still under 
system temperature and pressure, open the stop valve at the top of the 
column first of all, then open the valve at the bottom by a small amount to 
allow the column to slowly fill with liquid. 

During commissioning, check the probe/level column joint for leaks. 

8. 

Maintenance 

No routine maintenance is required other than periodically checking that 
the level indicated corresponds to the liquid level within the vessel.  For 
applications using R718 (water), if mineral deposits appear on the outside 
of the transmitter tube, these should be removed. 

4 to 20 mA 

Output Signal

Liquid Level

Reaction Time 

Summary of Contents for Danfoss AKS 41

Page 1: ...A 11 6 4 Signal Damping 11 6 5 Restore Factory Default Settings 12 7 Commissioning 12 8 Maintenance 12 9 Faults and Remedies 13 10 Spares 14 11 Appendix 1 AKS 41 Early Version 15 11 1 Measuring Test V...

Page 2: ...art of this publication may be reproduced or transmitted in any form or by any means electronic or mechanical including photocopying recording or by any information storage or retrieval system without...

Page 3: ...ls Part 1 1992 Specification for Presentation of Essential Information WARNING This denotes an immediate hazard with a high likelihood of personal injury or death if instructions including recommended...

Page 4: ...out the earlier version fitted with one green and one red LED can be found in Appendix 1 3 Operation The transmitter comprises consists of two parts an inner insulated electrode and an outer tube with...

Page 5: ...liquid level is registered as an increase in the rod s capacitance and hence results in a higher 4 to 20 mA output signal 4 Technical Data PARAMETER DETAILS General Enclosure IP 65 Max working press 1...

Page 6: ...HT MODEL INSERTION LENGTH B WEIGHT AKS 41U 6 152 mm 1 32 kg AKS 41 3 280 mm 1 7 kg AKS 41U 8 203 mm 1 41 kg AKS 41 5 500 mm 2 0 kg AKS 41U 12 305 mm 1 55 kg AKS 41 8 800 mm 2 4 kg AKS 41U 15 3 389 mm...

Page 7: ...Seal Outer Tube Plug can be mounted in four different positions Transmitter housing and tube can be separated without emptying the standpipe A B 1 BSP AKS 41 NPT AKS 41U Transmitter Housing Assembly...

Page 8: ...here is no voltage to the level transmitter Press the calibration push button and keep it depressed while refitting the connecting plug Release the push button the green LED is extinguished until the...

Page 9: ...ends 43 mm from the top gasket s contact face The liquid level transmitter has been factory calibrated to R717 ammonia so that the entire measuring range is utilised i e the transmitter s output sign...

Page 10: ...op of the rod measured from the gasket s contact face b Press the calibration push button and keep it depressed for approximately 5 seconds until the green LED stops flashing then release c Within the...

Page 11: ...n be measured b Bring the refrigerant liquid level to the desired maximum level c Press the calibration push button and keep it depressed for approximately 5 seconds until the green LED stops flashing...

Page 12: ...re Factory Default Settings To restore default settings press the calibration push button and keep it depressed for a minimum of 20 seconds until the green LED starts flashing Release the push button...

Page 13: ...e to gain access to the four screw terminals inside the plug where the four wires are connected Measure the resistance in the outer current loop between terminals 2 and 3 the plug must not be mounted...

Page 14: ...FAULT Output signal current is constant 4 mA Probable Cause Remedy Green LED flashing red LED also flashing early versions The transmitter is in setting mode Interrupt the supply voltage for about 10...

Page 15: ...t activated the green LED flashes When the programming button is activated the green LED follows the activation i e the green LED is On whenever the programming button is pressed Fig 7 AKS 41 Early Ve...

Page 16: ...arry out 12 2 step a first b Bring the liquid refrigerant to the level corresponding to the maximum limit of the measuring range i e the point on the rod where the transmitter s output signal is to be...

Page 17: ...16 75 mm A signal current of 6 mA therefore corresponds to a liquid level of 2 x 75 150 mm and a signal current of 12 x 75 900 mm As the liquid level can be adjusted between 100 and 950 mm it is poss...

Page 18: ...Danfoss AKS 41 Liquid Level Transmitter Publication 9 45 Section 9 Page 18 of 18 Issue 1 10 11 This page intentionally blank...

Reviews: