12. 

Adjustment (Early Version) 

12.1. 

Setting AKS 41 for the Refrigerant (Early Version) 

Same as the later version of the AKS 41; refer to 6.1.  The red LED 
‘flashes’ when the transmitter is in setting mode. 

12.2. 

Calibration for Minimum Liquid Level (Early Version) 

(a) 

There is a shorting strap provided at one of the two pins provided 
for calibration of 4 to 20 mA output signal.  Place this strap across 
the two pins so they are short-circuited.  The liquid level transmitter 
is now in calibration mode: green LED extinguished, red LED 
‘flashing’. 

(b) 

Bring the liquid refrigerant to the level corresponding to the lower 
limit of the measuring range, i.e. the point on the rod where the 
transmitter’s output signal is to be 4 mA.  The full length of the rod 
should be used if possible, so calibrate the lower limit with the 
liquid level below the end of the rod. 

(c) 

Press the calibration push-button then release within 3 seconds.  
The green LED will illuminate when the button is pressed. 

Wait 10 seconds.  The new minimum calibration has been saved to 
memory. 

(d) 

Unless the calibration of the maximum liquid level is to be carried 
out, remove the shorting strap from across the two pins and store 
by placing over one of the two pins. 

12.3. 

Calibration for Maximum Liquid Level (Early Version) 

(a) 

Normally, maximum calibration is done after minimum.  If this is not 
the case, carry out 12.2 step (a) first. 

(b) 

Bring the liquid refrigerant to the level corresponding to the 
maximum limit of the measuring range. i.e. the point on the rod 
where the transmitter’s output signal is to be 20 mA.  The full 
length of the rod should be used if possible, so calibrate the upper 
limit with the liquid level 45 mm below the top of the rod (measured 
from the top gasket’s contact face). 

(c) 

Press the calibration push-button then release within 3 seconds.  
The green LED will illuminate when the button is pressed. 

Wait 10 seconds.  The new maximum calibration has been saved 
to memory. 

(d) 

Remove the shorting strap from across the two pins and store by 
placing over one of the two pins. 

12.4. 

Calibration for Minimum and Maximum Points Other Than 4 mA and 
20 mA (Early Version) 

The usual minimum and maximum calibration points are 4 mA and 
20 mA, however, the transmitter can be calibrated at other points within 
the signal range.  This facility is especially useful if it is impractical to 
bring the liquid level to the maximum and minimum limits. 

It is necessary to measure the 4 to 20 mA output signal.  Dismantle the 
cap on the DIN connecting plug and pull it back a little on the cable to 
gain access to the four screw terminals inside the plug where the four 
wires are connected.  Connect a meter between terminals 2 and 3 so that 
the 4 to 20 mA output signal can be measured. 

There is a shorting strap provided at one of the two pins for calibration of 
4 to 20 mA output signal.  Place this strap across the two pins so they are 
short-circuited.  The liquid level transmitter is now in calibration mode: 
green LED extinguished, red LED ‘flashing’. 

Summary of Contents for Danfoss AKS 41

Page 1: ...A 11 6 4 Signal Damping 11 6 5 Restore Factory Default Settings 12 7 Commissioning 12 8 Maintenance 12 9 Faults and Remedies 13 10 Spares 14 11 Appendix 1 AKS 41 Early Version 15 11 1 Measuring Test V...

Page 2: ...art of this publication may be reproduced or transmitted in any form or by any means electronic or mechanical including photocopying recording or by any information storage or retrieval system without...

Page 3: ...ls Part 1 1992 Specification for Presentation of Essential Information WARNING This denotes an immediate hazard with a high likelihood of personal injury or death if instructions including recommended...

Page 4: ...out the earlier version fitted with one green and one red LED can be found in Appendix 1 3 Operation The transmitter comprises consists of two parts an inner insulated electrode and an outer tube with...

Page 5: ...liquid level is registered as an increase in the rod s capacitance and hence results in a higher 4 to 20 mA output signal 4 Technical Data PARAMETER DETAILS General Enclosure IP 65 Max working press 1...

Page 6: ...HT MODEL INSERTION LENGTH B WEIGHT AKS 41U 6 152 mm 1 32 kg AKS 41 3 280 mm 1 7 kg AKS 41U 8 203 mm 1 41 kg AKS 41 5 500 mm 2 0 kg AKS 41U 12 305 mm 1 55 kg AKS 41 8 800 mm 2 4 kg AKS 41U 15 3 389 mm...

Page 7: ...Seal Outer Tube Plug can be mounted in four different positions Transmitter housing and tube can be separated without emptying the standpipe A B 1 BSP AKS 41 NPT AKS 41U Transmitter Housing Assembly...

Page 8: ...here is no voltage to the level transmitter Press the calibration push button and keep it depressed while refitting the connecting plug Release the push button the green LED is extinguished until the...

Page 9: ...ends 43 mm from the top gasket s contact face The liquid level transmitter has been factory calibrated to R717 ammonia so that the entire measuring range is utilised i e the transmitter s output sign...

Page 10: ...op of the rod measured from the gasket s contact face b Press the calibration push button and keep it depressed for approximately 5 seconds until the green LED stops flashing then release c Within the...

Page 11: ...n be measured b Bring the refrigerant liquid level to the desired maximum level c Press the calibration push button and keep it depressed for approximately 5 seconds until the green LED stops flashing...

Page 12: ...re Factory Default Settings To restore default settings press the calibration push button and keep it depressed for a minimum of 20 seconds until the green LED starts flashing Release the push button...

Page 13: ...e to gain access to the four screw terminals inside the plug where the four wires are connected Measure the resistance in the outer current loop between terminals 2 and 3 the plug must not be mounted...

Page 14: ...FAULT Output signal current is constant 4 mA Probable Cause Remedy Green LED flashing red LED also flashing early versions The transmitter is in setting mode Interrupt the supply voltage for about 10...

Page 15: ...t activated the green LED flashes When the programming button is activated the green LED follows the activation i e the green LED is On whenever the programming button is pressed Fig 7 AKS 41 Early Ve...

Page 16: ...arry out 12 2 step a first b Bring the liquid refrigerant to the level corresponding to the maximum limit of the measuring range i e the point on the rod where the transmitter s output signal is to be...

Page 17: ...16 75 mm A signal current of 6 mA therefore corresponds to a liquid level of 2 x 75 150 mm and a signal current of 12 x 75 900 mm As the liquid level can be adjusted between 100 and 950 mm it is poss...

Page 18: ...Danfoss AKS 41 Liquid Level Transmitter Publication 9 45 Section 9 Page 18 of 18 Issue 1 10 11 This page intentionally blank...

Reviews: