Danfoss AKS 41 Liquid Level Transmitter
Publication 9-45
Section 9
Page 6 of 18
Issue 1 : 10/11
5.
Installation
Allow adequate space for transmitter removal.
Locate a gasket seal under the hexagon portion of the transmitter body,
insert into the level column taking care not to bend the transmitter.
Tighten with a spanner on the hexagon flats provided.
Wiring connections to the probe are shown in Fig 2, also refer to the
control panel wiring diagrams specific to the application. Segregate
control wiring from power wiring, do not run together.
Fig 2 Wiring
AKS
41U
AKS
41
M
ODEL
I
NSERTION
L
ENGTH
A
W
EIGHT
M
ODEL
I
NSERTION
L
ENGTH
B
W
EIGHT
AKS 41U-6
152 mm
1.32 kg
AKS 41-3
280 mm
1.7 kg
AKS 41U-8
203 mm
1.41 kg
AKS 41-5
500 mm
2.0 kg
AKS 41U-12
305 mm
1.55 kg
AKS 41-8
800 mm
2.4 kg
AKS 41U-15.3
389 mm
1.72 kg
AKS 41-10
1000 mm
2.7 kg
AKS 41U-19.2
488 mm
1.82 kg
AKS 41-12
1200 mm
3.1 kg
AKS 41U-23.1
587 mm
1.96 kg
AKS 41-15
1500 mm
3.5 kg
AKS 41U-30
762 mm
2.22 kg
AKS 41-17
1700 mm
3.8 kg
AKS 41U-35
889 mm
2.38 kg
AKS 41-22
2200 mm
4.6 kg
AKS 41U-45
1143 mm
2.71 kg
AKS 41-30
3000 mm
5.8 kg
AKS 41U-55
1397 mm
3.1 kg
AKS 41U-65
1651 mm
3.5 kg
AKS 41U-85
2159 mm
4.3 kg
AKS 41U-105
2667 mm
4.93 kg
AKS 41U-120
3048 mm
5.7 kg
Fig 3 AKS 41 and AKS 41U Liquid Level Transmitters
EKC 347 Electronic
Liquid Level Controller
4 to 20 mA
Signal
24 V dc or
24 V ac 50/60 Hz
24 V ac
DIN Plug
Connection