4⁰C
1⁰C
1⁰C
2⁰C
Standby mode
Only in combination with a suitable heat
pump and control valve for heating and
cooling
The device automatically enters cooling mode when the water temperature is 2°C/4°F below the
room temperature. If the differential between room and water temperature is less than 1
°
C/2°F, the
device will automatically switch to standby. The unit starts at the last selected speed(1, 2 or 3), if the
water temperature < 24 ̊C.
Make sure that the thermostat head is set to ‘K’ when cooling.
The unit is in standby. The unit automatically starts a new cycle if the preset temperature is rea-
ched.
The device automatically enters heating mode when the water temperature is 4
°
C/7°F above the
room temperature. If the differential between room and water temperature is less than 1
°
C/2°F higher
than the room temperature, the device will automatically switch to standby. The unit starts at the last
selected speed(1, 2 or 3), if the water temperature > 28 ̊C.
De breeze mode is switched on and off manually. The auto-change-over is disabled as long as the
breeze mode is active. The unit starts at the last selected speed (1, 2 of 3), regardless of the water
temperature.
5. OPERATION AUTO-CHANGE-OVER