Table 7: LED indicators
Icon next to
the LED
LED name
Color
Status
Indication
Fire alarm
Red
Steady ON
The panel is in “Fire alarm” state
Sounders ON
Red
Steady ON
The sounder outputs are ON
Blinking
The sounder outputs are in
delayed activation and will activate
automatically after the delay time
has expired.
Fire brigade ON
Red
Steady ON
The FR outputs are ON
Blinking
The FIRE ROUTING outputs are
in delayed activation and will
activate automatically after the
delay time has expired.
Delays OFF
Yellow
Steady ON
The delays to outputs are active.
An alarm is processed, SND and
FR outputs will have a delayed
activation.
Blinking
The system is under delayed
activation state. SND and/or FR
outputs will activate automatically
after the delay time has expired.
Fault
Yellow
Steady ON
The system is in fault functional
condition.
System fault
Yellow
Steady ON
The CIE has detected a major
malfunction in one of its
subsystems.
Disable condition
Yellow
Steady ON
There are disabled elements in the
system.
Test condition
Yellow
Steady ON
The CIE is under test functional
condition. There is at least one
element under test.
Sounder fault/disable/test
Yellow
Steady ON
One or more sounder have been
disabled or are under test
Blinking
There is a fault affecting sounders.
FR output
fault/disable/test
Yellow
Steady ON
One or more FR outputs have
been disabled or are under test
Blinking
There is a fault affecting FR
outputs
Power ON
Green
Steady ON
The CIE is supplied with power
(from mains or from the battery)