JBE-P2L1 Panel Manual V1.2 EN
Page 15
Release Date: January 5, 2021
Rev 01
4.3.4 Set address descriptions
Enter a brief description of the location for each loop device. This information is aimed for a quick
identification of each loop device and will be presented in the main screen in case of a fire or fault (see
4.5.1.2).
4.3.5 Assign outputs to activation groups
After auto-registration, all output devices will have been assigned to output group 003. Assign outputs to
group 001 (EN 54 Sounders), group 002 (EN 54 Fire routing) or to groups 003 to 400 (freely programmable).
Note that, in a default configuration, output group 003 does not have an activation rule configured. Therefore,
alarms will not be triggered unless the rule is programmed from the Advanced Installation menu (see 4.5.1.6).
4.3.6 Change passwords
Select the desired passwords for user access level 2 and user access level 3.