JBE-P2L1 Panel Manual V1.2 EN
Page 4
Release Date: January 5, 2021
Rev 01
3
Technical Specifications
This chapter will review the technical specification and provide detailed data on the overall system, and the
electrical, mechanical and environmental characteristics of the Draco fire control panel.
3.1
General Data
Table 1: General Panel Data
System dimensions
Number of detection loops
1 or 2
User-selectable detection loop topologies
Class A (ring) or Class B (stub)
24 V outputs to field devices
2
Maximum number of detection zones
400
Maximum number of output groups
400
Connection to field devices
Maximum loop distance
2.000 m
Recommended cable type
2 x 1.5 mm
2
unshielded twisted pair
Maximum number of addressable points (Free
mix of detectors, MCP, IO, sounders)
200 per Class A loop (max 2x200)
Detection loop voltage
JBE pulsed protocol (20 to 30 Vpp)
Detection loop available current
200 mA
DC outputs to field devices
2 x 2 A @ 24 Vdc
Field cable access to panel cabinet
Ø20 mm knockouts (18x)
Alarm & Fault relay outputs
Connection type
Normally-Open voltage-free relay
Electrical contact ratings
2A @ 30 VDC
3.2
Power supply
Table 2: Power supply parameters
Power supply
Mains voltage
AC 230 V (196
– 253 V)
Mains fuse
2.5 A slow acting
Power rating (mains)
2.5 A max
Max. sustained DC output current (I
max a
)
4 A
Max. alarm DC output current (I
max b
)
5.5 A
3.3
Batteries
Table 3: Battery Features
Batteries
Quantity
2 batteries (sold separately)
Approved battery types
Primary cabinet (6.3 mm Faston tab terminal)
•
Yuasa NP7-12LFR
•
Yuasa NP12-12FR
With optional battery box kit (Ø5 mm ring terminal)
•
Yuasa NP17-12IFR
Float charge compensation
-36 mV/ºC
Internal battery resistance
Max 1
Ω