![Jacuzzi J-DREAM Owner'S Manual Download Page 5](http://html1.mh-extra.com/html/jacuzzi/j-dream/j-dream_owners-manual_3196708005.webp)
READ ALL INSTRUCTIONS BEFORE BEGINNING ASSEMBLY AND INSTALLATION
General Assembly Information
The J-Dream shower unit is installed either into a niche or a corner with the drain at the side of the unit as you face
the shower door. This manual explains the step by step procedures for assembly, installation, and operation of the
J-Dream shower system. After installing the drain and providing the water supply stub-out and electrical supply,
assemble the free standing shower unit away from the walls of the room. Next connect and static test the water supply
lines. The electrical connections should then be completed before the unit is moved into final position. Recheck the
drain fit and complete the assembly before final testing.
Room Construction: Important
The room where the shower unit is to be located must be constructed of materials that can withstand excessive
amounts of moisture and condensation. Large amounts of steam can be released into the room when the shower door
is opened. Providing natural or forced ventilation of the room will help maintain comfort and minimize moisture damage
to the building. Jacuzzi Whirlpool Bath is not responsible for damages resulting from excess moisture or water spillage.
Consult an architect or engineer for aid in designing your interior structure.
Do not install heat lamps directly above the shower unit as the heat from the lamps may deform the clear top.
Water Supply
The water supply must be capable of delivering 3 gallons per minute minimum to the unit within a pressure range of
20–65 psi (1.4–4.6 BAR). Pressures in excess of 65 psi (4.6 BAR) must be reduced with a regulator in the supply line.
This is the flow of water and pressure required to ensure adequate performance of the J-Dream. This not the water
consumption rate.
NOTE: Do not provide less than the minimum flow specified. Negative pressure under certain conditions might cause
a health hazard by fouling the house potable water supply.
Electrical Power
See Specifications for power required. Power supplied to the unit must be through a *GFCI-protected, dedicated circuit
with proper bonding and grounding. The GFCI must be located in an area that will allow access for frequent testing.
* GFCI ( Ground Fault Circuit Interrupter) is also known as an ELCB ( Earth Leakage Circuit Breaker). This device must
be a type approved by electrical codes and standards to protect users from potential electrical hazards.
J-Dream Owner’s Manual
3