ELECTRICAL REQUIREMENTS
SPECIFICATIONS
3
NOTE: Typical Electrical Circuit is based upon (1) 125% of the full amperage load of the machine and (2) typical
fixedtrip circuit breaker sizes as listed in the NEC 2002 Edition. Local codes may require more stringent protection
than what is displayed here. Always verify with your electrical service contractor that your circuit protection is
adequate and meets all applicable national and local codes. These numbers are provided in this manual simply
for reference and may change without notice at any given time.
Volts
Phase
Freq
Rinse Heater
Ratings
Total Amps
Typical Electrical
Circuit
415
3
60
12kW
28A
35AMP
415
3
60
14kW
30A
40AMP
208
1
60
12kW@240V
75A
100AMP
208
1
60
12kW@240V
82A
110AMP
230
1
60
12kW@240V
81A
110AMP
230
1
60
14kW@240V
90A
125AMP
208
3
60
12kW@240V
48A
60AMP
208
3
60
14kW@240V
52A
70AMP
230
3
60
12kW@240V
52A
70AMP
230
3
60
14kW@240V
57A
80AMP
460
3
60
12kW@480V
24A
30AMP
460
3
60
14kW@480V
26A
35AMP
TEMPSTAR HH:
Volts
Phase
Freq
Rinse Heater
Ratings
Total Amps
Typical Electrical
Circuit
208
1
60
N/A
31A
35AMP
230
1
60
N/A
33A
35AMP
208
3
60
N/A
23A
25AMP
230
3
60
N/A
24A
35AMP
460
3
60
N/A
10A
15AMP
TEMPSTAR HH NB & TEMPSTAR HH LT:
Volts
Phase
Freq
Rinse Heater
Ratings
Total Amps
Typical Electrical
Circuit
208
1
60
N/A
12A
15AMP
230
1
60
N/A
12A
15AMP
208
3
60
N/A
12A
15AMP
230
3
60
N/A
12A
15AMP
TEMPSTAR HH S:
Summary of Contents for TempStar Series
Page 2: ......
Page 28: ...PARTS 22 TOP MOUNTED CONTROL BOX ASSEMBLY 30 28 29 25 22 21 26 33 34 36 1...
Page 36: ...PARTS HOOD ASSEMBLY 30 1 5 4 2 3 6 7 10 8 9...
Page 60: ...PARTS 460 VOLT MACHINE TRANSFORMER MOUNTING BOX 54...
Page 61: ...PARTS PARTS 55 EXHAUST FAN CONTROL OPTION...
Page 66: ...ELECTRICAL SCHEMATICS SOLID STATE TEMPSTAR HH TOP MOUNT CONTROLS 208 230V 60HZ 1 3 PHASE 60...
Page 67: ...ELECTRICAL SCHEMATICS 61 TEMPSTAR HH UNIVERSAL TIMER 208 230V 60HZ 1 3 PHASE...
Page 68: ...ELECTRICAL SCHEMATICS 62 SOLID STATE TEMPSTAR HH TOP MOUNT W CYCLE SWITCHES 460V 60HZ 3 PHASE...
Page 69: ...ELECTRICAL SCHEMATICS TEMPSTAR HH UNIVERSAL TIMER 460V 60HZ 3 PHASE 63...
Page 70: ...ELECTRICAL SCHEMATICS TEMPSTAR HH S UNIVERSAL TIMER 208 230V 60HZ 1 3 PHASE 64...
Page 71: ...ELECTRICAL SCHEMATICS TEMPSTAR HH 208 230V 60HZ 1 3 PHASE 65...
Page 72: ...ELECTRICAL SCHEMATICS TEMPSTAR HH 460V 60HZ 3 PHASE 66...
Page 73: ...ELECTRICAL SCHEMATICS TEMPSTAR HH S 208 230V 60HZ 1 3 PHASE 67...
Page 74: ...ELECTRICAL SCHEMATICS TEMPSTAR HH NB 208V 230V 50 60HZ 1 PHASE 68...
Page 75: ...ELECTRICAL SCHEMATICS TEMPSTAR HH NB LT 208V 230V 50 60HZ 1 PHASE 69...
Page 76: ...70 ELECTRICAL SCHEMATICS OPTIONS SDI OPTION...
Page 77: ...ELECTRICAL SCHEMATICS OPTIONS EXHAUST FAN HOOKUP DRAIN QUENCH OPTIONS 71...
Page 78: ...Tempstar HH Series Installation Operation Technical Manual 07610 002 23 32 Issued 09 14 07...