background image

SPECIFICATIONS

Input Voltage

24 VAC  50/60 Hz

Relay Rating

24 VAC @ 1Amp maximum
per relay

Operating Temperature

32° F to 122° F

Operating RH

0-95% (non-condensing)

Storage Temperature

32° F to 105° F

Size

4-7/16” W x 4-1/16” H x 7/8” D

LCD Display Size

2-3/4” W x 1-7/8” H

Temperature Sensor

10K NTC type 2

Voltage

20-30 VAC

Resistance

10k

@ 77 F

Tolerance

+/- 3% @ 77 F

Stage Delays

Minimum temperature change
over time

Timed Upstage Delay

5 - 90 minutes

Short-cycle Delay

Off to 4 minutes

Display Resolution

0.1° F

Control Range

Off to 105° F

Outdoor Air Temperature Range

-10° F to 140° F

Back Light

Blue EL (Electro Luminescent)

Optimized Start/Stop Method

Time to start vs. temperature
differential

Communications Protocol

Modbus

Approvals

FCC (Part 15) (Pending)

Warranty

5 years

Ω

°

°

The T-32-P can be configured for 3-speed fan and

single setpoint control.

For information regarding these features, contact

Jackson Systems at 1-888-652-9663

REMOTE SENSOR INSTALLATION INSTRUCTIONS

The T-32-P can use an indoor remote sensor or
multiple sensors for temperature averaging or as
an outdoor sensor for temperature display or a
control function depending upon the thermostat
configuration.

Locate the sensor in the same manner as a
thermostat. Mount the sensor 18” away from any
outside wall. Do not install the sensor behind
doors, in corners or other dead air spaces. Keep
the sensor away from direct air flow, supply
registers or near sources

INDOOR SENSOR INSTALLATION

of heat such as lamps

and appliances. The maximum wire length from the
sensor to the thermostat is 300 feet. Use a
separate 18-2 thermostat cable for sensor wiring.
Prior to wiring the sensor to the thermostat, use an
ohm-meter or multimeter to measure the
resistance of the sensor. Measure at the end of the
wires that will connect to the thermostat.

OUTDOOR SENSOR INSTALLATION

Mount the sensor on a vertical exterior surface
below an overhang. Choose a location protected
from direct sunlight and exposure to excessive
moisture. Follow the same wiring and test
procedures as installing an indoor sensor.

SENSOR CALIBRATION CHART

Temperature

(

°F)

Resistance

(

k )

Ω

Temperature

(

°F)

Resistance

(

k )

Ω

30

40

50

60

34.6

26.1

19.9

15.3

70

80

90

100

11.9

9.4

7.4

5.9

Confirm the resistance value (within 5%) to the
temperature where the sensor is mounted.
Disconnect power to the thermostat when wiring
the sensor to the ‘T’ and ‘T’ terminals. Strip only as
much insulation off of the wires as necessary to
provide a good contact with the terminals. The
sensor is not polarity specific so either sensor lead
may be connected to either terminal on the

BASIC TROUBLE SHOOTING

SYMPTOM

POSSIBLE FAULT AND REMEDY

Thermostat
displays wrong
temperature.

The T-32-P can display in either Fahrenheit
or Celsius. Change CF=C or F in the
Advanced Installer menu.

The fan continues
to run after a
heating or cooling
call is satisfied.

The thermostat is set to Fan ON. Set the
thermostat to Auto Fan. The fan purge
mode is set to run the fan for a fixed period
of time after the equipment shuts off.
Change the FP value in the Advanced
Installer menu.

Some buttons on
the thermostat do
not function.

Lock values have been set. Refer to LC
settings in the Advance Installer menu.

Thermostat clock
does not keep
proper time.

Make sure that the plastic tab on the
internal fitted battery is removed so that the
battery is operational.

Wrench icon flashes
on LCD

This is not a fault. Commissioning mode is
enabled and time delays are overridden.
Change CD=1 to CD=0 in the Advanced

Outdoor temperature
does not display.
Dashes (---) appear
on the LCD.

Check wiring to outdoor sensor. Make sure
that TT=OA in the Advanced Installer menu.

Heating or Cooling is
flashing while the
HVAC system is
running.

This is not a fault. The T-32-P has a built-in
minimum equipment run time of either 2 or 6
minutes. Sw6 may set for 6 minutes (ON)
which is keeping the equipment on after the
thermostat reaches setpoint. Try setting

Lock icon flashes
when trying to set a
higher heating or
lower cooling
temperature.

This is not a fault. HL and CL restrict the
heating and cooling setpoints. The limit
values can be changed in the Advanced
Installer menu.

11

Summary of Contents for Comfort System T-32-P

Page 1: ...Installation Manual Comfort System T 32 P Universal Thermostat TM For Version 2 19 and 2 20 ...

Page 2: ...s without notice All rights reserved Jackson Systems LLC 2009 Intellectual rights apply 5418 Elmwood Avenue Indianapolis Indiana 46203 888 652 9663 www jacksonsystems com INTRODUCTION 2 TABLE OF CONTENTS Introduction 2 Getting started 3 Installing the thermostat 3 Disassembly 3 Thermostat location 3 Mounting the subbase 3 Terminal designations 4 Typical system wiring diagram 4 Heat only 4 1 heat 1...

Page 3: ... in a location that represents the ambient space temperature Do not install the thermostat in an area where drafts are present near the floor behind doors or on an external wall Avoid placing the thermostat in areas where the air movement is limited affected by direct sunlight or other areas not typical of the temperature in the space When mounting the T 32 P be aware that drafts may travel down w...

Page 4: ...AY 24 V W2 G3 Y2 G2 W1 O B Y1 G1 R 24 24C B A T T HEAT 1 RELAY FAN 1 RELAY MODBUS TT TERMINALS LINE COMP 1 RELAY COMP 2 RELAY HEAT 2 RELAY 24 V 2 HEAT 2 COOL Switch Settings Sw1 OFF Fan Relay Sw2 OFF Heat Cool Sw3 ON Two Stage Sw4 OFF Equipment Controls Fan Sw5 Installer Preference OFF No Short Cycle Protection ON 4 Minute Short Cycle Protection Sw6 User Preference OFF Non programmable ON Programm...

Page 5: ...ference Off 2 Minute Minimum Run Time ON 6 Minute Minimum Run Time Sw8 ON Separate Heating and Cooling Setpoints W2 G3 Y2 G2 W1 O B Y1 G1 R 24 24C B A T T REV VALVE FAN 1 RELAY MODBUS TT TERMINALS LINE COMP 1 RELAY FOSSIL FUEL 24 V 2 HEAT 1 COOL DUAL FUEL Switch Settings Sw1 OFF Fan Relay Sw2 ON Heat Pump Sw3 OFF Single Stage Sw4 Reversing Valve OFF O RV Energized in Cooling ON B RV Energized in H...

Page 6: ...Fan Mode or Reversing Valve Fan Mode Reversing Valve Sw5 Short Cycle Timer Sw6 Thermostat Operation Switch 4 sets the fan logic for heat cool systems or sets the reversing valve configuration for heat pump systems For gas or oil systems equipment controls fan in heating mode set the switch to the OFF position factory default For electric systems thermostat controls fan in heating mode set the swit...

Page 7: ... OR BOTH TT RS For remote sensor 1 or more remote indoor sensor without the onboard sensor being used TT OA For outdoor remote sensor connection TT DA Sends measured temperature from remote sensor via modbus but does not display the value on the LCD TT OC For connecting dry contact switch Replaces user setpoints with pre programmed cooling OC and heating OH setpoints TT OF For connecting dry conta...

Page 8: ...nsor calibration Adjustable 9 F CO 55 Cooling OFF temperature Only works if TT OA with outdoor sensor When outdoor temperature falls below setpoint cooling will shut off Adjustable from 41 F 122 F SP S8 88 8S C2 C8 ADVANCED INSTALLER SETTINGS MENU ADVANCED INSTALLER SETTINGS MENU TT TERMINAL FUNCTIONS The T and T terminals on the T 32 P are primarily used for wiring either an indoor or an outdoor ...

Page 9: ...itch is closed the T 32 P will turn off and the word will flash on the LCD When the switch is opened the thermostat will return to the user settings For remote override TT OC in the Advanced Installer menu Override setpoints are programmed in the Advanced Installer menu using OC Cooling setpoint and OH Heating setpoint When the switch is closed the user setpoints are replaced by the pre programmed...

Page 10: ...ermostat TESTING HEAT PUMP OPERATION E Heat E Heating When the T 32 P is configured for heat pump operation testing is the same as for a conventional heating and cooling system with the exception that the fan relay is energized on a call for both heating and cooling When the thermostat is placed in the emergency heat mode will be displayed on the LCD When the W2 relay is energized will be displaye...

Page 11: ... moisture Follow the same wiring and test procedures as installing an indoor sensor SENSOR CALIBRATION CHART Temperature F Resistance k Ω Temperature F Resistance k Ω 30 40 50 60 34 6 26 1 19 9 15 3 70 80 90 100 11 9 9 4 7 4 5 9 Confirm the resistance value within 5 to the temperature where the sensor is mounted Disconnect power to the thermostat when wiring the sensor to the T and T terminals Str...

Reviews: