background image

Symbol

Default

Function

SS

0

Start/Stop Mode.
(Controlled by thermostat program)

SS=1 - Thermostat in Start only mode
per call by Modbus Master.
SS=2 - Thermostat in Stop only mode
per call by Modbus Master.

OF

0

Leave at factory default

RS

50

Response Time.
(Leave at factory default)

TS

0

Factory Test Mode OFF.

TS=1 - Display configuration code.
TS=2 - Step cycle all relays in
sequence.
TS=3 - Reset software to factory
defaults.
(Press fan button to initiate)

SS

08
8S

8S

HO

75

Heating OFF temperature. Only works if
TT=OA with outdoor sensor. When
outdoor temperature rises above
setpoint, heating will shut off.
(Adjustable from 41° F - 122° F)

HB

55

High Balance Point.
Only works if TT=OA with outdoor
sensor and H3=FF
for fossil fuel. W2 auxiliary heat
is locked out when temperature rises
above HB setpoint.
(Adjustable from 32° F - 122° F)

LB

35

Low Balance Point.
Only works if TT=OA with outdoor
sensor and H3=FF
for fossil fuel. W2 auxiliary heat is
locked out when temperature falls
below LB setpoint.
(Adjustable from 15° F - 77° F)

FT

OF

Replace or clean filter.

(Off to 900 hours in 100 hour

increments)

AD

1

Modbus Address.
(Adjustable from 0 to 32)

H8

H8

L8

88

A8

Symbol   Default

Function

SP

1

1.4° F differential for stage 1.

SP=2 - 1.9° F differential.
SP=3 - 2.4° F differential.

SD

1

1.4° F differential for stage 2.

SP=2 - 1.9° F differential.
SP=3 - 2.4° F differential.

DT

20

Upstage Timer.
(Adjustable from 10 - 90 minutes in
5 minute increments) Only works if
thermostat has not called for 2nd or
3rd stage. (Sw3=ON)

OS

1

Adaptive Recovery ON.

OS-0 = Adaptive Recovery OFF.

C2

0.0

Remote sensor calibration.
(Adju/- 9° F)

CO

55

Cooling OFF temperature. Only
works if TT-OA with outdoor sensor.
When outdoor temperature falls below
setpoint, cooling will shut off.
(Adjustable from 41° F - 122°F)

SP

S8

88

8S

C2

C8

ADVANCED INSTALLER SETTINGS MENU

ADVANCED INSTALLER SETTINGS MENU

TT TERMINAL FUNCTIONS

The ‘T’ and ‘T’ terminals on the T-32-P are primarily
used for wiring either an indoor or an outdoor remote
sensor. The terminals are not polarity dependent. The
terminals can also be used for other functions such as
remote ON/OFF switching of various control functions
depending upon thermostat configuration. Each
configuration requires setup in the Advanced Installer
menu.

There are two type of remote sensors. The T-32-S1 is
a single sensor that can be used indoors or outdoors.
The T-32-S2 contains two sensors. A combination of
both sensors can be used for indoor temperature
averaging to simplify wiring.

REMOTE SENSORS

W2

G3

Y2

G2

W1

O/B

Y1

G1

R

24       24C        B

A

T          T

T-32-S1 SENSOR

FIGURE 6

OUTDOOR SENSOR WIRING

When the T-32-S1 is used as an outdoor sensor, the
T-32-P will display the outside air temperature. In the
Advanced Installer menu, TT=OA. The outdoor sensor
can also be used for high and low balance point
control in dual fuel systems. Use separate 18-2
thermostat cable when wiring the sensor to the
thermostat. If the outdoor sensor fails, or is not wired
properly, two dashes will appear on the LCD where
the outside temperature would normally be displayed.

(Figure 6)

8

S3

1

1.4

S3

° F differential for stage 3.

S3=2 - 1.9° F differential.
S3=3 - 2.4° F differential.

SU

10                    Leave at factory default.

su

BD

19.2

Baud Rate.

BD=4.8
BD=9.6

CD

0

Commissioning Mode
OFF.
(All time delays active)

CD=1- Commissioning
Mode ON.
(All time delays inactive)

88

C8

Summary of Contents for Comfort System T-32-P

Page 1: ...Installation Manual Comfort System T 32 P Universal Thermostat TM For Version 2 19 and 2 20 ...

Page 2: ...s without notice All rights reserved Jackson Systems LLC 2009 Intellectual rights apply 5418 Elmwood Avenue Indianapolis Indiana 46203 888 652 9663 www jacksonsystems com INTRODUCTION 2 TABLE OF CONTENTS Introduction 2 Getting started 3 Installing the thermostat 3 Disassembly 3 Thermostat location 3 Mounting the subbase 3 Terminal designations 4 Typical system wiring diagram 4 Heat only 4 1 heat 1...

Page 3: ... in a location that represents the ambient space temperature Do not install the thermostat in an area where drafts are present near the floor behind doors or on an external wall Avoid placing the thermostat in areas where the air movement is limited affected by direct sunlight or other areas not typical of the temperature in the space When mounting the T 32 P be aware that drafts may travel down w...

Page 4: ...AY 24 V W2 G3 Y2 G2 W1 O B Y1 G1 R 24 24C B A T T HEAT 1 RELAY FAN 1 RELAY MODBUS TT TERMINALS LINE COMP 1 RELAY COMP 2 RELAY HEAT 2 RELAY 24 V 2 HEAT 2 COOL Switch Settings Sw1 OFF Fan Relay Sw2 OFF Heat Cool Sw3 ON Two Stage Sw4 OFF Equipment Controls Fan Sw5 Installer Preference OFF No Short Cycle Protection ON 4 Minute Short Cycle Protection Sw6 User Preference OFF Non programmable ON Programm...

Page 5: ...ference Off 2 Minute Minimum Run Time ON 6 Minute Minimum Run Time Sw8 ON Separate Heating and Cooling Setpoints W2 G3 Y2 G2 W1 O B Y1 G1 R 24 24C B A T T REV VALVE FAN 1 RELAY MODBUS TT TERMINALS LINE COMP 1 RELAY FOSSIL FUEL 24 V 2 HEAT 1 COOL DUAL FUEL Switch Settings Sw1 OFF Fan Relay Sw2 ON Heat Pump Sw3 OFF Single Stage Sw4 Reversing Valve OFF O RV Energized in Cooling ON B RV Energized in H...

Page 6: ...Fan Mode or Reversing Valve Fan Mode Reversing Valve Sw5 Short Cycle Timer Sw6 Thermostat Operation Switch 4 sets the fan logic for heat cool systems or sets the reversing valve configuration for heat pump systems For gas or oil systems equipment controls fan in heating mode set the switch to the OFF position factory default For electric systems thermostat controls fan in heating mode set the swit...

Page 7: ... OR BOTH TT RS For remote sensor 1 or more remote indoor sensor without the onboard sensor being used TT OA For outdoor remote sensor connection TT DA Sends measured temperature from remote sensor via modbus but does not display the value on the LCD TT OC For connecting dry contact switch Replaces user setpoints with pre programmed cooling OC and heating OH setpoints TT OF For connecting dry conta...

Page 8: ...nsor calibration Adjustable 9 F CO 55 Cooling OFF temperature Only works if TT OA with outdoor sensor When outdoor temperature falls below setpoint cooling will shut off Adjustable from 41 F 122 F SP S8 88 8S C2 C8 ADVANCED INSTALLER SETTINGS MENU ADVANCED INSTALLER SETTINGS MENU TT TERMINAL FUNCTIONS The T and T terminals on the T 32 P are primarily used for wiring either an indoor or an outdoor ...

Page 9: ...itch is closed the T 32 P will turn off and the word will flash on the LCD When the switch is opened the thermostat will return to the user settings For remote override TT OC in the Advanced Installer menu Override setpoints are programmed in the Advanced Installer menu using OC Cooling setpoint and OH Heating setpoint When the switch is closed the user setpoints are replaced by the pre programmed...

Page 10: ...ermostat TESTING HEAT PUMP OPERATION E Heat E Heating When the T 32 P is configured for heat pump operation testing is the same as for a conventional heating and cooling system with the exception that the fan relay is energized on a call for both heating and cooling When the thermostat is placed in the emergency heat mode will be displayed on the LCD When the W2 relay is energized will be displaye...

Page 11: ... moisture Follow the same wiring and test procedures as installing an indoor sensor SENSOR CALIBRATION CHART Temperature F Resistance k Ω Temperature F Resistance k Ω 30 40 50 60 34 6 26 1 19 9 15 3 70 80 90 100 11 9 9 4 7 4 5 9 Confirm the resistance value within 5 to the temperature where the sensor is mounted Disconnect power to the thermostat when wiring the sensor to the T and T terminals Str...

Reviews: