34
3.2.3
VENT CONFIGURATION
3.2.3.1
LEGEND
3.2.3.2
CONDITIONS THAT MUST ALWAYS BE MET
• Total vent length, including elbows (see 3.2.3.3), must not exceed 40 ft. H + V
≤
40 ft.
• The first 8 ft. of vent (from the fireplace) must always be covered with the insulating sleeve provided with the
fireplace; no matter the model or configuration type.
• The first 6 in. of vent (from the fireplace) must be vertical.
• The horizontal run, including elbow equivalents (see 3.2.3.3), must not exceed 3 times the vertical rise when it
is greater than or equal to 1.33 ft. (16 in.) and less than or equal to 10 ft.
H
≤
3xV only if 1.33 ft. (16 in.)
≤
V
≤
10 ft.
Exception: 6 in.
≤
V
≤
16 in. H
max.
= 48 in. (4 ft.)
• Maximum of 4 elbows for the entire exhaust length.
• Minimum of 1 ft. (0.3 m) is required between two vent elbows.
• No vent section should have a downward slope.
3.2.3.3
ELBOW EQUIVALENT FOR HORIZONTAL VENT LENGTH
Elbow angle
Horizontal vent length
equivalent (H
e
)
in.
ft.
1º
0.4
0.033
15º
6
0.5
30º
12
1
45º
18
1.5
90º
36
3
Note
1
: The first elbow has a value of 0 in horizontal vent length. The above table is valid for the 2nd, 3rd, and
4th elbows.
CAUTION:
No vent section should slope downwards (from the fireplace to the exterior vent outlet).
-
≤
: less than or equal
-
≥
: greater than or equal
- <: less than
- >: greater than
- V: vertical rise
- H: horizontal run
Summary of Contents for suroit RGV-25
Page 17: ...17 2 3 FIREPLACE DIMENSIONS 2 3 1 LOO RGR 25 INSERT 2 3 2 MISTRAL RGP 25 PENINSULA...
Page 18: ...18 2 3 3 AUSTER RGCG 25 LEFT CORNER 2 3 4 MOUSSON RGCD 25 RIGHT CORNER...
Page 19: ...19 2 3 5 SIROCCO RGB 25 PANORAMIC 2 3 6 PAMPERO RGC 25 CENTRAL...
Page 22: ...22 3 1 1 2 LOO RGR 25 INSERT WITH SIDE EXIT 3 1 1 3 LOO RGR 25 INSERT WITH TOP EXIT...
Page 56: ...56 7 3 ELECTRICAL DIAGRAM OF THE SmartCase...
Page 70: ......