Value of Zero indicates normal, healthy operation. Any other value indicates a subsystem or multiple
subsystem errors. See below.
Binary
Designation(s)
Decimal
Value
Error Meaning
Bit 0 = 1
1
GPS Communication (Comm) Error
Bit 1 = 1
2
Charge Controller Comm Error
Bits 0 and 1 = 1
3
GPS Comm and Charge Controller Comm Error
Bit 2 = 1
4
Motor Comm Error
Bits 0 and 2 = 1
5
GPS Comm and Motor Comm Error
Bits 1 and 2 = 1
6
Charge Controller Comm and Motor Comm Error
Bits 0, 1, and 2 = 1
7
GPS Comm, Charge Controller Comm, and Motor Comm Error
Bit 3 = 1
8
Analog Out of Range (OOR) Error
Bits 0 and 3 = 1
9
GPS Comm and Analog OOR Error
Bits 1 and 3 = 1
10
Charge Controller Comm and Analog OOR Error
Bits 0, 1, and 3 = 1
11
GPS Comm, Charge Controller Comm, and Analog OOR Error
Bits 2 and 3 = 1
12
Motor Comm and Analog OOR Error
Bits 0, 2, and 3 = 1
13
GPS Comm, Motor Comm, and Analog OOR Error
Bits 1, 2, and 3 = 1
14
Charge Controller Comm, Motor Comm, and Analog OOR Error
Bits 0, 1, 2, and 3 = 1
15
GPS Comm, Charge Controller Comm, Motor Comm, and Analog OOR
Error
For Customer Service, contact Ixom Watercare, Inc. Main Office and Service Center at 866-437-8076.
©2022 IXOM Watercare Inc. | www.ixomwatercare.com | 866 - 437 - 8076 | [email protected]
SolarBee SCADA
Integration
System Status for SolarBee SCADA Integration
Register Address 7 (Base 10)
2075_10326_20220110
O&M_SB5000PW_10272_20220119 - 61