Alarm Message
Alarm Message
ID
ID
Problem/Conditions
Problem/Conditions
Possible Cause
Possible Cause
Possible Solution(s) or Next Step(s)
Possible Solution(s) or Next Step(s)
Loss of Flow Detected
300
System has momentarily lost
ability to confirm proper flows
Non-critical warning
If issue persists, or becomes more
frequent, could signify maintenance is
required on flow verification sensors.
See Maintenance documentation for
more details.
Loss of Circulation
Detected
301
System has momentarily lost
circulation
Non-critical warning
If issue persists, or becomes more
frequent, could signify issues with Pre-
Mix Tank, Sample Pump, or Return
Pump.
See Maintenance documenta-
tion for more details.
Daily Volume Limit
Reached
302
System has fed the maxi-
mum allowed chemical
volume in 24 hour period.
Incorrect settings
Non-critical warning. Will self-correct
clear at 0:00. Verify feed settings
are appropriate for recent flows and
residual levels.
Increased chemical demand
Low Bulk Chlorine
Level Detected
303
Level reported is below alert
setpoint
Low level in chlorine bulk
tank
Non-critical warning. Ensure low
level is not due to leaks/spills. Refill if
necessary.
Incorrect settings/scaling
factors
Check sensor/transducer scaling, and
thresholds at
Base > Configure > Data.
Low Bulk Ammonia
Level Detected
304
Level reported is below alert
setpoint
Low level in ammonia bulk
tank
Non-critical warning. Ensure low
level is not due to leaks/spills. Refill if
necessary.
Incorrect settings/scaling
factors
Check sensor/transducer scaling, and
thresholds at
Base > Configure > Data.
Low Monitored Tank
Level Detected
305
Level reported is below alert
setpoint
Low level in monitored tank
Non-critical warning. Ensure low
level is not due to leaks/spills. Refill if
necessary.
Incorrect settings/scaling
factors
Check sensor/transducer scaling, and
thresholds at
Base > Configure > Data.
The table below summarizes system Warnings. The following may self-correct, but could adversely impact system
performance.
Warnings: