![IXOM ResidualHQ Control Manual Download Page 28](http://html1.mh-extra.com/html/ixom/residualhq/residualhq_control-manual_2098828028.webp)
Name
Addr. R/W Default
Mult.
Units Description
Setting Range
0
1
0
65,535
0
65,535
0
65,535
0
65,535
0
65,535
Monitored Tank
Level
96
R/W 1
10
Monitored tank level
Bulk Chlorine Level 94
R/W 1
10
Bulk Chlorine tank level
Bulk Ammonia
Level
95
R/W 1
10
Bulk Ammonia tank level
Min. Chlorine
Alarm Setpoint
92
R/W 1
1000
ppm
Minimum setpoint for Total Chlorine level alarm
Max. Chlorine
Alarm Setpoint
93
R/W 1
1000
ppm
Maximum setpoint for Total Chlorine level alarm
Degas Enable
91
R/W 1
1
Enable the degassing scheme. Exercises valves to mitigate gas accumulation in lines,
valves, etc.
©2022 IXOM Watercare Inc. | www.ixomwatercare.com | 866 - 437 - 8076 | [email protected]
Registers
Modbus Registers
Defaults, Values and Descriptions
10319_20220119
ControlManual_ResidualHQ_10380_20220809a - 26