IXOM ResidualHQ Control Manual Download Page 12

Overview

Users with Configuration permissions will have access to the following screens and menus. These menus should be

accessed with caution, as many settings will directly change the operation of the system in automated modes, resulting

in changes to automated decision-making processes and actions. 

Base ► Configure ► System

Name

Name

Units

Units

Def.

Def.

Low

Low

High

High

Description

Description

Motor Current Limit

%

10

0

100

Motor over/under current limit (Sample Pump and Mixer monitor)

Sample Current 

Setpoint

amps

12.00

0.00

20.00 Sample Pump typical operating current setpoint

Mixer Current      

Setpoint

amps

12.00

0.00

20.00 Mixer typical operating current setpoint

Chlorine Degas 

Enable

T/F

T

Enable chlorine degassing scheme

Ammonia Degas 

Enable

T/F

F

Enable ammonia degassing scheme

Remote Enable

T/F

F

Enable remote control (Via Modbus RTU)

Modbus ID

1

1

256

Low level alert for bulk chlorine storage. Units and Low/High limits

user-defined.

Modbus Reload

T/F

F

Modbus RTU reload request. Required after Modbus ID change.

Screen Timeout

secs

300

0

9999

Seconds of inactivity before automatic logout

Local Log Start

T/F

F

Start/restart local (HMI USB) datalogging

Local Log Stop

T/F

F

Stop local (HMI USB) datalogging

Set System Time

Set system (local) time.  Enter value, press button to save

Fatal Fault Definition T/F

F

Stops sample if: Ammonia valve routine error

Fatal Fault cont’d

T/F

F

Stops sample if: Chlorine valve routine error

Fatal Fault cont’d

T/F

F

Stops sample if: Chemical feed routine error

Fatal Fault cont’d

T/F

F

Stops sample if: Mixer monitoring routine error

Fatal Fault cont’d

T/F

F

Stops sample if: Unaccounted bulk chemical change

Fatal Fault cont’d

T/F

F

Stops sample if: Flow verification failure

Fatal Fault cont’d

T/F

F

Stops sample if: Degassing routine error

Fatal Fault cont’d

T/F

F

Total Chlorine readings out of range

K Factor Rinse

3785.41

K factor value for Rinse flow meter

K Factor Chlorine

3785.41

K factor value for chlorine flow meter

K factor ammonia

3785.41

K factor value for chlorine flow meter

Retry attempts

8

Circulation retry attempts after a nonfatal error has occurred

Sleep Timer

Minutes

10

Minutes system can be powered down before turning off circulation on 

reboot

Total Chlorine Max.

ppm

4.0

Alarm if total chlorine is above this value

Total Chlorine Min.

ppm

0.5

Alarm if total chlorine is below this value

Remote Tank input

T/F

F

Use customer input for tank data over modbus

©2022 IXOM Watercare Inc. | www.ixomwatercare.com | 866 - 437 - 8076 | [email protected]

Menu

Configuration

Configuration Menu

Parameter Information

10360_20220119

ControlManual_ResidualHQ_10380_20220809a - 10

Summary of Contents for ResidualHQ

Page 1: ...atercare Inc www ixomwatercare com 866 437 8076 watercare ixom com 2022 IXOM Watercare Inc www ixomwatercare com 866 437 8076 watercare ixom com ControlManual_ResidualHQ_10380_20220809a ResidualHQ Con...

Page 2: ...014_20220110 ResidualHQ Control Manual Safety 1 Getting Started 4 Menu Layout 6 Menus Monitor 7 Menus Operation 8 Menus Configuration 10 Menus Administration 13 Initial Settings 14 Modbus Communicatio...

Page 3: ...id hazards by following these safety instructions and applying some ordinary common sense when operating or servicing this unit Keep in mind that full operator attention and alertness are required whe...

Page 4: ...UIPMENT CONTAINS HIGH VOLTAGE ELECTRICAL SHOCK CAN CAUSE SERIOUS OR FATAL INJURY ONLY QUALIFIED PERSONNEL SHOULD ATTEMPT PLACEMENT OPERATION AND MAINTENANCE OF ELECTRICAL EQUIPMENT REMOVE ALL SOURCES...

Page 5: ...ative OSHA and local regulations while installing and performing any maintenance to the mixer circulation equipment Key OSHA Compliance Standards that must be followed and not limited to are 1910 146...

Page 6: ...n authorization hierarchy to prevent un wanted tampering or control Users are granted permissions by a System Administrator which may be maintained locally to manage user profiles When the icon is sel...

Page 7: ...riate access a log in dialogue will appear first If the value does not appear to change once it has been entered and confirmed it is likely an invalid entry was made See Parameter Information for spec...

Page 8: ...General Operation Parameters Automated Management Parameters Trending and Historical Data Parameters User Administration and Runtime Control Controller Diagnostics Home Login Monitor Operate Configur...

Page 9: ...ority of which are represented by pilot lights under system conditions Overview Users with Monitor permissions will have access to the following screens and menus The Monitor menus are available to qu...

Page 10: ...cified manual dose Start Stop Start or Stop the manual dose Chemical Selection Chemical solutions available to be manually dosed Base Operate Name Description Mode Selection Graphical buttons allowing...

Page 11: ...hemes Use with extreme caution Remote Enable Switch controlling remote control If enabled no Maintenance operations will be allowed This protects the system from being manually configured without pers...

Page 12: ...ging Set System Time Set system local time Enter value press button to save Fatal Fault Definition T F F Stops sample if Ammonia valve routine error Fatal Fault cont d T F F Stops sample if Chlorine v...

Page 13: ...ns 60 0 32767 Duration of wait period after feed has been stopped before making trend or threshold determinations Automated Management Mode decisions Determination Hysteresis mins 5 Number of minutes...

Page 14: ...tor Tank 15 Low level alert for monitored tank Units and Low High limits user defined Tank Sensor Units User defined String for Tank Sensor Units Max of 4 characters Tank Sensor Min 0 0 User defined F...

Page 15: ...dvanced diagnostic information from PLC to be displayed Useful for viewing loss of power or other runtime events Stop Runtime Button allowing runtime control of HMI Pressing will allow editing of HMI...

Page 16: ...the monitored tank While not always possible the mixer should be allowed to operate for 24 hours in order for chlorine demand to stabilize Step 3 Begin Corrections The system is loaded with default s...

Page 17: ...rting point 30 additional capacity may be used for many applications For initial settings this daily volume should be distributed into 2 4 Corrections Per Day If low turnover or incoming water is gene...

Page 18: ...ly impacting the existing residual levels Step 4 Continued Tuning Once the system has made several corrections the Determination Wait Time should be matched to the dynamic conditions of the tank accou...

Page 19: ...nessed results feed rates used and mixing turnover times Crossover Target o In high use situations where recovery time is limited a Crossover Target may be employed Should be set at a residual level e...

Page 20: ...2022 IXOM Watercare Inc www ixomwatercare com 866 437 8076 watercare ixom com Initial Settings Initial Settings 10386_20220809 ControlManual_ResidualHQ_10380_20220809a 18...

Page 21: ...2022 IXOM Watercare Inc www ixomwatercare com 866 437 8076 watercare ixom com Initial Settings Initial Settings 10386_20220809 ControlManual_ResidualHQ_10380_20220809a 19...

Page 22: ...the command ex 2 95 100 295 In certain instances registers are reported as hexadecimal denoted by 0x values to represent status information Additionally certain registers indicate relevant informatio...

Page 23: ...tablish Wait Period 0x008F Error Detected R Automated Management Mode Status Residual Range Warning Word Output Word System Operational Mode System OK Error Word 4 6 2 1 Each respective bit indicates...

Page 24: ...orine 22 R 100 Gals Total daily volume from 00 00 of chlorine injection Daily Ammonia 23 R 100 Gals Total daily volume from 00 00 of ammonia injection Param Ch ID 24 R 1 Modbus Register Address of the...

Page 25: ...lume of chlorine injection Total Vol Ammonia 33 R 100 Gal Total volume of ammonia injection Free Chlorine 34 R 1000 ppm Free Chlorine Residual Recent Average 2022 IXOM Watercare Inc www ixomwatercare...

Page 26: ...ed Modes 1 1 5 30 68 R W 720 R W 64 If last dose was not made within this timeout duration prior actions will not be considered for Automated Management decisions Mins Mins Length of time system waits...

Page 27: ...00 1000 Gals Once this limit is reached the system will no longer allow itself to feed until the next day 0 500 Amount of time after system has stopped chemical feed before making trend or threshold d...

Page 28: ...larm Setpoint 92 R W 1 1000 ppm Minimum setpoint for Total Chlorine level alarm Max Chlorine Alarm Setpoint 93 R W 1 1000 ppm Maximum setpoint for Total Chlorine level alarm Degas Enable 91 R W 1 1 En...

Page 29: ...events are recorded in the Alarm Log Each is managed in a circular format overwriting the oldest values Event Log Alarm Log VarName Variable Name Time_ms Value 1E6 Days Since 1 1 1900 TimeString Time...

Page 30: ...Error 103 Monitored current is out of range over undercurrent See Mixer documentation for details Sample Pump Error 104 Monitored current is out of range over undercurrent Current Limit Nuisance Trip...

Page 31: ...erify input to controller by viewing Base Operate Maintenance or Base Admin I O Low High Flow Condition Verify flooded suction to chemical inputs When actively feeding chemical the Rinse Pressure Regu...

Page 32: ...rine Level Detected 303 Level reported is below alert setpoint Low level in chlorine bulk tank Non critical warning Ensure low level is not due to leaks spills Refill if necessary Incorrect settings s...

Page 33: ...and the world Contact us today to discuss your water quality and service needs EVERYONE DESERVES GREAT CUSTOMER SUPPORT Ixom Watercare earns customer trust with unparalleled service start to finish Ev...