8.3 Meny – ”Settings”
In Setup menu are all settings made.
Parameter
Range
Description
Default
Fan mode
Stopp
Normal
Forcerad
Auto
Unit stopped
Unit operates with SA and EA at normal speed
Unit operates with SA and EA at forced speed
Unit operates with fan speed according to time
schedule
Stopp
Setp. Main
0-60
°
C
Main setpoint room/extract air or climate adapted
control.
20
°
C
Setp. Supply air
0-60
°
C
Setpoint supply air temperature
20
°
C
Minv. Supply air
0-60
°
C
Minimum supply air temperature
16
°
C
Maxv. Supply air
0-60
°
C
Maximum supply air temperature
28
°
C
Alarm temp. fail
0-60
°
C
Deviation limit from setpoint for supply air temperature,
a B-alarm is set up after more than 30 minutes
deviation.
An A-alarm is set up and unit stops if temperature
drops more than 5° below low limit.
5
°
C
SA normal
0-100%
SA peed at normal speed
40%
EA normal
0-100%
EA peed at normal speed
40%
SA forced
0-100%
SA peed at forced speed
80%
EA forced
0-100%
EA peed at forced speed
80%
Outd. Temp fan
normal
-30 - +30
°
C Fan speed limits to normal speed at outdoor temp.
below set value.
Climate adapted control: Low outdoor temperature, fan
speed normal at and below this point. See fig.
-25
°
C
0
°
C
Outd. Temp fan
forced
-30 - +30
°
C Only at Climate adapted control:
High outdoor temperature, fan speed forced at and
above this point.
The point where controller shift between supply and
extract air control See fig.
14
°
C
Outd comp
summer Temp 1
-30 - +30
°
C Setpoint for start of summer compensation (at this point
there is no compensation)
25
°
C
Outd comp
summer Temp 2
-30 - +30
°
C Setpoint for full summer compensation (at this point
compensation has is full influence on temp. control)
30
°
C
Outd comp
summer Comp
-30 - +30
°
C The value that compensation would achieve at “Temp
2” summer.
0
°
C
Outd comp winter
Temp 1
-30 - +30
°
C Setpoint for full winter compensation (at this point
compensation has is full influence on temp. control)
-20
°
C
Outd comp winter
Temp 2
-30 - +30
°
C Setpoint for start of winter compensation (at this point
there is no compensation)
+5
°
C
Outd comp winter
Comp
-30 - +30
°
C The value that compensation would achieve at “Temp
1” winter.
0
°
C
DX cool start
0 – 100%
Switch on point.
Visible only when Cool battery is selected as Installed.
20%
DX cool stop
0 – 100%
Switch off point.
Visible only when Cool battery is selected as Installed.
5%