PerformaxIQEasyPerformaxIQEasySpeed_UM_9752154110_NL_D_GB_V1_2
67
,
- [
(n)x
“
Remote on/off source
”
select
Remote
or
Fieldbus
]
6.8 (De)activating Datalogging
If desired, the Manager can log data regarding the operation of the bar.
To (de)activate this data logging, the parameter
Datalogging
has to be changed.
For detailed information on datalogging, please refer to the manual Manager IQ Easy.
- [
(n)x
“
Data logging
”
select
On
or
Off
]
6.9 Setting clean bar warning level (expert mode)
After calibrating the bar (6.3), the IQ Easy bar will continuously monitor the effectiveness of the
bar. Should the effectiveness get below the set
Clean bar warning
level due to dirt, covering or
other cause, a warning (orange LEDs on the bar and orange background for the icon on the
Manager) will be generated on the Manager.
By default, this level is set standard to 50 %, but it can be set to a different value in specific
cases.
- [,
(n)x
“
Clean bar warning
level”
slide slider or with
to the
desired value and confirm with
]
6.10 Commissioning the anti-static bar with a 24 V power supply
If the bar is connected to a 24 V power supply without the Manager, the bar will not have IQ
functionality. The bar can however be switched on/off remotely with the pin on the M12
connector and feedback will be provided on whether the high voltage is active on the
corresponding pin of the M12 connector (see figure 7).
- Remove the protection cover of the anti-static bar.
- Switch on the power supply of the anti-static bar.
- Connect 24 V DC to the Remote On/Off input of the bar*.
- When 24 V DC supply voltage is connected and the Remote On/Off input is activated, the
anti-static bar will be switched on.
* With a desktop power supply provided by Simco-Ion, the Remote on/off is already connected internally with the
24 V supply voltage. If this power supply is used, the bar will hence be activated as soon as the power supply is
switched on.