IQ Easy Speed-T & Hybrid-T
Static Neutralizing Bars
Standalone
The IQ Easy Static Neutralizing Bar may be operated without a control station.
In this case, the IQ Easy Static Bar will enter Standalone operating mode. In
Standalone Mode, the IQ Easy Static Bar operates in Fixed mode ionization with
the standard 50/50 balance. Wiring normally used for communication is internally
switched to provide fault output.
Fault Output
If the bar is operating normally (no red indicator light), the output pin 4 (black) and
pin 2 (white) connected together, will be energized with +24 VDC (50 mA max). If
the bar is in a fault mode (red indicator light lit steady) the output (pin 4 and pin
2 connected together) will not be energized; 0 VDC. Voltages are referenced to pin
3 (blue 0V/ground).
Note
: Pin 4 (black) and pin 2 (white) MUST be connected together in standalone
mode.
NOTE –
Fault Output only functions in standalone mode.
Figure 6: IQ Easy Static Bar Wiring Color Code
The wiring color code shown in Figure 6 is typical for 5-pin M12 A-coded
connection cables.
Figure 7: IQ Easy Static Bar Standalone Wiring
NOTE –
Electrical connections shall be made by qualified personnel in
accordance with national and local electric codes using only Recognized
connectors appropriate for 22 AWG wires and rated for no less than 24
VDC 4A.