Operation Manual - Hobart 2400 Compact – 120 / 140 / 180 kVA
Set-up Lock / Output Mode / Compensation
Document no. 578.430AB
Page 57 of 75
7.17 Earth Leakage Delay
This submenu is used in conjunction with the Earth Leakage Level submenu. The default value is 1000
ms.
Go into the Setup Menu and then scroll up or down to the Earth Leakage Delay submenu. Press the
center
●
button to enter the submenu and then press the
●
button again to allow the value to be changed.
Press the up or down arrow buttons to change the selection. Press the center
●
button to record the new
value. Press the LEFT arrow button to exit the submenu and return to the submenu list.
7.18 Real Time Clock Setup
This set of submenus allows the user to adjust the internal clock to the correct local time.
Go into the Setup Menu and then scroll up or down to the Real Time Clock Setup submenu. Press the
center
●
button to enter the submenu and then press the
●
button again to allow the value to be changed.
Press the up or down arrow buttons to change the selection. Press the center
●
button to record the new
value. Press the LEFT arrow button to exit the submenu and return to the submenu list.
7.19 Date/Time Format
The date and time format that is displayed on all of the screens and reports can be adjusted using this
submenu. The selection is a 24 hour clock and DD:MM:YYYY date format or a 12 hour clock with the
MM:DD:YYYY date format.
Go into the Setup Menu and then scroll up or down to the Date/Time Format submenu. Press the center
●
button to enter the submenu and then press the
●
button again to allow the value to be changed. Press
the up or down arrow buttons to change the selection. Press the center
●
button to record the new value.
Press the LEFT arrow button to exit the submenu and return to the submenu list.
7.20 Ethernet Configuration
This set of submenus allows the user to enter the Ethernet IP address, Subnet Mask, Gateway address
and DNS1 values for TCP/IP communications with a BMS or RMS central monitoring system.
Go into the Setup Menu and then scroll up or down to the Ethernet Configuration submenu. Press the
center
●
button to enter the submenu and then press the
●
button again to allow the value to be changed.
Press the up or down arrow buttons to change the selection. Press the center
●
button to record the new
value. Press the LEFT arrow button to exit the submenu and return to the submenu list.
7.21 Modbus Slave Address
If the unit will be part of an RS-485 Modbus RTU BMS/RMS monitoring system, it must be assigned a
Modbus Slave Address. This submenu allows the user to enter the slave address.
OM2252