IU_MAP_MANUAL_01i01_ENG
15 /20
5.
Technical parameters
5.1.
Input circuits
5.1.1.
Arc detection optic inputs
Number of inputs
6
Connector type
Avago
Maximum length of single sensor fiber connection
15 m
5.1.2.
Binary inputs
Number of inputs
2
Input type
voltage
Maximum length of single cable connection
< 3 m
Nominal voltage (4 versions)
24 V DC
110 V DC
220 V DC
230 V AC
Nominal voltage DC 24 V
Minimum excitation voltage
DC 22 V
Maximu de-excitation voltage
DC 19 V
Current consumption before excitation
< 11 mA
Current consumption after excitation
≤ 5 mA
Nominal voltage DC 110V
Minimum excitation voltage
DC 90 V
Maximu de-excitation voltage
DC 50 V
Current consumption before excitation
< 4 mA
Current consumption after excitation
≤ 2 mA
Nominal voltage DC 220 V
Minimum excitation voltage
DC 160 V
Maximu de-excitation voltage
DC 150 V
Current consumption before excitation
< 2 mA
Current consumption after excitation
≤ 1 mA
Nominal voltage AC 230 V
Minimum excitation voltage
AC 125 V
Maximu de-excitation voltage
AC 119 V
Current consumption before excitation
< 2 mA
Current consumption after excitation
≤ 1 mA
5.2.
Output circuits
5.2.1.
Fiber outputs
Number of outputs
1
Connector type
Avago
Maximum length of single sensor fiber connection
15 m