- Limit out:

If a 4-20 mA output is used, this parameter allows you to limit the output value so as to limit the maximum 
dosing pump flow rate.

- Pump:

Enter the rated dosing pump flow rate to record the dosed flow rate in the data logger.

- Hysteresis

For neutralisation with acid and base, enables a margin to be set around the setpoint where no regulation 
will take place.

which the output will be ON for the proportional part of the time corresponding to the regulating output.

4.4.2 Advanced control configuration. PIQ control

For adjustment of pH, the control system operates using a PI algorithm. The setting parameters for this 
control are in the PI CONTROL menu

PH CONTROL

CONTROL

PI CONTROL

ENT

PH PI CONTROL

PIQ (PpH) 

   

    030

Kp

:

      20

Ki

:

    

      30

delay:    

 

 020 

s

Q test:

      00.00 m3

h

- PIQ (PpH):

The PIQ control mode to adjust pH is a PI algorithm conditioned on the flow rate of water to be treated. 
Initial dosing proportional to the water rate is set using the PpH parameter, and is subsequently corrected 
by means of a PI approximation curve. This system, which can only be activated with independent pumps 
(type mA outlets for acid/alkaline dosing), ensures pH stability even with highly variable flow rates and 
provides greater agility in reaching and maintaining the

setpoint.

PpH=0 PI control. PIQ control disabled.
PpH= 1 - 200 Acid dosing will be proportional to the water flow rate with setpoint adjustment by means 
of a PI algorithm. The proportion is indicated by the PpH parameter and is referenced to 100,000 units of 
water flow.

Summary of Contents for WTRTEC RED

Page 1: ...WTRTEC ENGLISH...

Page 2: ...4 4 1 Activation of the control 8 4 4 2 Advanced control configuration PIQ control 9 4 5 Alarms 11 4 5 1 pH alarms 11 4 5 2 Zero flow alarm 11 4 5 3 Flow detector alarm 11 4 6 Configuration of the re...

Page 3: ...oning and maintaining the equipment must follow the instructions in this manual with special attention to the detailed recommendations and warnings The specific instructions for the use of the chemica...

Page 4: ...or base dosing pumps WTRTEC Red enables monitoring remote management and historical logging by means of a mobile web application A communications Gate Ref 01 006 is needed for this which can be conne...

Page 5: ...ted Flow meter power supply 12 VDC 100 mA pH sensor 0 00 14 00 Isolated pH EC temperature sensor 0 0 100 C 32 0 212 F PT100 Remote input ON OFF 12 24 V AC DC Flow detector ON OFF NPN isolated Outputs...

Page 6: ...gulation output no device detected on the 4 20 mA output Flashing regulation outputs both remote control deactivated or no device connected to the 4 20 mA outputs Press ENTER to edit the setpoint or m...

Page 7: ...buffer value using the up down arrows Insert the sensor into the point 1 buffer wait until the sensor reading is stable and confirm with ENTER Repeat the operation with the point 2 buffer Before putt...

Page 8: ...ecirculating tank The regulating output establishes 5 minute cycles in PH CONTROL Out 2 4 20 mA 2 Limit out 2 080 Pump 2 1200 l h PH CONTROL OUT 1 OUT 2 PH CONTROL Control ON Out 1 4 20 mA 1 Limit out...

Page 9: ...ng parameters for this control are in the PI CONTROL menu PH CONTROL CONTROL PI CONTROL ENT PH PI CONTROL PIQ PpH 030 Kp 20 Ki 30 T delay 020 s Q test 00 00 m3h PIQ PpH The PIQ control mode to adjust...

Page 10: ...mulated error and enables reading stabilisation once the setpoint value has been achieved It is only valid for in line controls For recirculating controls it must be Ki 0 T delay seconds T delay is th...

Page 11: ...top enables shutting down of the dosing control output for the alarmed control parameter for all or none 4 5 2 Zero flow alarm An alarm can be set to warn that there is no flow in the main pipe If the...

Page 12: ...ENT 4 6 Configuration of the register outputs If any of the 4 20 mA analogue control outputs is unused these can be used to be configured as outputs for logging any sensor readings To do this the outp...

Page 13: ...inute ENT CONFIG COMMUNICATIONS Node 02 Baudrate 1200 Parity N Stop bits 1 CONFIG SET UP COMUNICATIONS CHECK MONITOR 4 7 3 Information on the unit and monitor This screen displays information on the e...

Page 14: ...21 0 5 INSTALLATION A place protected from water away from heat and direct sunlight must be chosen for installation 5 1 Installation diagram In line pH control In tank pH control Device Mixer ACID ACI...

Page 15: ...event abrupt starts 13 1 4 5 6 7 8 8 9 3 2 9 15 10 11 12 14 110 240 VAC power supply 12 VDC power supply RemoteON OFFinput canbeactivatedwith12 24VAC DC pH alarm output Relay Flow rate alarm output Re...

Page 16: ...nnect the pumps see Installing and Wiring 2 Equipment calibration and configuration Calibrate the sensors pH flow meter etc see Calibration Configure the equipment Setpoint Type of control Installatio...

Page 17: ...17 Maintenance 7 MAINTENANCE 45602 45603 45604 45606 40604 44619 45606 45607 45 615 M12 33654...

Page 18: ...1 pitch black 2 44619 Female angled terminal strip 3 pins 5 pitch 2 40604 Female angled terminal strip 6 pins 5 pitch 1 45605 Female angled terminal strip 3 pins 7 5 pitch 1 45 615 M12 Hose cable M12...

Page 19: ...nstruction manual Ant n Planas Manager WARRANTY I T C S L guarantees the product specified in this document for a period of 1 year from the date of purchase against all manufacturing or material defec...

Page 20: ...ginal Manual Ed 6 3 2020 EN C Vall s 26 Pol Ind Can Bernades Subir P O Box 60 08130 Santa Perp tua de Mogoda BARCELONA SPAIN Tel 34 93 5443040 Fax 34 93 5443161 e mail itc itc es www itc dosing pumps...

Reviews: