background image

11

Configuration

4.5 Alarms

4.5.1 pH alarms

To set the alarms, enter the upper and lower tolerance values with respect to the value entered as the 
setpoint and the time from which, with the reading outside tolerance range, the alarm must be activated. If 
the value = 0, the alarm is disabled. The alarms will activate only if the Control is ON.

pH

SP

07.00

CAL

CONTROL

ALARM

REGISTER

PH ALARM

Reset: N

o

Stop:  pH

 

pH +

 1.00

            025 

s

pH -

 0.50

            060 

s

ENT

pH + 1.00: the alarm will activate when 

the reading is 1.00 above the setpoint 

value for 25 seconds

pH - 0.5: the alarm will activate when 

the reading is 0.50 below the setpoint 

for 60 seconds

Reset: enables automatic alarm reset when the reading is back within the permissible values.

Stop: enables shutting down of the dosing control output for the alarmed control parameter, for all or none. 

4.5.2 Zero flow alarm

An alarm can be set to warn that there is no flow in the main pipe. 

If the value = 0, the alarm is disabled.

Reset: 

enables automatic alarm reset when the reading is back within the permissible values.

Stop:

 enables the dosing control outputs to be shut down. 

4.5.3 Flow detector alarm

When an external sensor holder is used through which a water sample is made to pass, and this has a 
flow detector, an alarm can be configured to warn in the event that no water sample reaches the external 

sensor holder. 

If the value = 0, the alarm is disabled.

ENT

m3h

0.20 %

SP

CAL

CONTROL

ALARM

ALARM DETECTOR

REGISTER

      Q 

ALARM 

o

Stop:  None

Q = 0

            200 

s

Reset: N

Bear in mind that if there are any filters between the injection point and the sensor, the calculation of 10 
metres x 1 m/s = 10 seconds will no longer be valid.

Summary of Contents for WTRTEC RED

Page 1: ...WTRTEC ENGLISH...

Page 2: ...4 4 1 Activation of the control 8 4 4 2 Advanced control configuration PIQ control 9 4 5 Alarms 11 4 5 1 pH alarms 11 4 5 2 Zero flow alarm 11 4 5 3 Flow detector alarm 11 4 6 Configuration of the re...

Page 3: ...oning and maintaining the equipment must follow the instructions in this manual with special attention to the detailed recommendations and warnings The specific instructions for the use of the chemica...

Page 4: ...or base dosing pumps WTRTEC Red enables monitoring remote management and historical logging by means of a mobile web application A communications Gate Ref 01 006 is needed for this which can be conne...

Page 5: ...ted Flow meter power supply 12 VDC 100 mA pH sensor 0 00 14 00 Isolated pH EC temperature sensor 0 0 100 C 32 0 212 F PT100 Remote input ON OFF 12 24 V AC DC Flow detector ON OFF NPN isolated Outputs...

Page 6: ...gulation output no device detected on the 4 20 mA output Flashing regulation outputs both remote control deactivated or no device connected to the 4 20 mA outputs Press ENTER to edit the setpoint or m...

Page 7: ...buffer value using the up down arrows Insert the sensor into the point 1 buffer wait until the sensor reading is stable and confirm with ENTER Repeat the operation with the point 2 buffer Before putt...

Page 8: ...ecirculating tank The regulating output establishes 5 minute cycles in PH CONTROL Out 2 4 20 mA 2 Limit out 2 080 Pump 2 1200 l h PH CONTROL OUT 1 OUT 2 PH CONTROL Control ON Out 1 4 20 mA 1 Limit out...

Page 9: ...ng parameters for this control are in the PI CONTROL menu PH CONTROL CONTROL PI CONTROL ENT PH PI CONTROL PIQ PpH 030 Kp 20 Ki 30 T delay 020 s Q test 00 00 m3h PIQ PpH The PIQ control mode to adjust...

Page 10: ...mulated error and enables reading stabilisation once the setpoint value has been achieved It is only valid for in line controls For recirculating controls it must be Ki 0 T delay seconds T delay is th...

Page 11: ...top enables shutting down of the dosing control output for the alarmed control parameter for all or none 4 5 2 Zero flow alarm An alarm can be set to warn that there is no flow in the main pipe If the...

Page 12: ...ENT 4 6 Configuration of the register outputs If any of the 4 20 mA analogue control outputs is unused these can be used to be configured as outputs for logging any sensor readings To do this the outp...

Page 13: ...inute ENT CONFIG COMMUNICATIONS Node 02 Baudrate 1200 Parity N Stop bits 1 CONFIG SET UP COMUNICATIONS CHECK MONITOR 4 7 3 Information on the unit and monitor This screen displays information on the e...

Page 14: ...21 0 5 INSTALLATION A place protected from water away from heat and direct sunlight must be chosen for installation 5 1 Installation diagram In line pH control In tank pH control Device Mixer ACID ACI...

Page 15: ...event abrupt starts 13 1 4 5 6 7 8 8 9 3 2 9 15 10 11 12 14 110 240 VAC power supply 12 VDC power supply RemoteON OFFinput canbeactivatedwith12 24VAC DC pH alarm output Relay Flow rate alarm output Re...

Page 16: ...nnect the pumps see Installing and Wiring 2 Equipment calibration and configuration Calibrate the sensors pH flow meter etc see Calibration Configure the equipment Setpoint Type of control Installatio...

Page 17: ...17 Maintenance 7 MAINTENANCE 45602 45603 45604 45606 40604 44619 45606 45607 45 615 M12 33654...

Page 18: ...1 pitch black 2 44619 Female angled terminal strip 3 pins 5 pitch 2 40604 Female angled terminal strip 6 pins 5 pitch 1 45605 Female angled terminal strip 3 pins 7 5 pitch 1 45 615 M12 Hose cable M12...

Page 19: ...nstruction manual Ant n Planas Manager WARRANTY I T C S L guarantees the product specified in this document for a period of 1 year from the date of purchase against all manufacturing or material defec...

Page 20: ...ginal Manual Ed 6 3 2020 EN C Vall s 26 Pol Ind Can Bernades Subir P O Box 60 08130 Santa Perp tua de Mogoda BARCELONA SPAIN Tel 34 93 5443040 Fax 34 93 5443161 e mail itc itc es www itc dosing pumps...

Reviews: