1 1/2”
MIN
1 1/2”
MIN
24” MI
N
Damper Beam
Behind Noncombustible
Facing Material
Drywall Flush With
Firebox Front With 1 1/2”
Clearance To Framing
Framing Protrudes Past
Firebox Front
9”
14
Flush Wall Finish Detail
Magnum 86072 Series fireplaces are designed to be installed so that the rough front face of the firebox and damper beam
project into the room approximately one-half inch (1/2”) beyond the face of the rough framing members that create the room’s wall
surface.
Noncombustible facing material must span framing members above the fireplace opening for drywall to keep the required
twenty four inches (24”) above the firebox opening top; It is after this noncombustible material that framing members can be placed
as shown above. Nine inches (9”) on each side of the firebox opening is also required to be covered in noncombustible material.
(Figure 11).
Important: Do not build a frame wall in front of the Magnum 86072 firebox and damper beam. (Figure 12)
FIGURE 11
FIGURE 12