28
Damping
Reduces fluctuations in the display output
1 ... 255 s
Metric / Imp
Use metric or imperial units for entered data
In/Output
Type
Select from list ↑↓
Current out
Source
Off
Channel 1
System
Units
Select from list ↑↓
Min Value
Min. process variable (PV) value that corresponds
to 0/4 mA
Max Value
Max. process variable (PV) value that corre-
sponds to 20 mA
Damping
Additional smoothing of the current output, the
higher the damping factor, 1 ... 255 s
Span
0-20mA or 4-20mA
Error
Defines output behaviour in the event of error
Select from list ↑↓
Hold (last value for specified time), 3.8mA,
21.0mA
Open
Collector Out
Mode
Yes –
Pulse output on
No –
Pulse output off
Pulse Value
Totaliser value of selected PV at which a pulse is
generated, e.g. PV = [m3/h], Pulse Value = 10, a
pulse is output every 10 m3
0.01 ... 1000
Pulse Width
Width of the pulse
30 ... 999 ms
Calc. Max
This is the calculated max. number of pulses per
second., i.e. the max. pulse rate in Hz
Voltage out
Source
Off
Channel 1
System
Units
Select from list ↑↓
Min Value
Min. process variable (PV) value that corresponds
to 0v
Max Value
Max. process variable (PV) value that corre-
sponds to 10v
Damping
Additional smoothing of the current output, the
higher the damping factor, 1 ... 255 s
Error
Defines output behaviour in the event of error
Select from list ↑↓
Frequency out
Source
Off
Channel 1
System
Units
Select from list ↑↓
Min Value
Min. process variable (PV) value that corresponds
to minimum frequency
Max Value
Max. process variable (PV) value that corre-
sponds to maximum frequency
Damping
Additional smoothing of the current output, the
higher the damping factor, 1 ... 255 s
Error
Defines output behaviour in the event of error
Select from list ↑↓
Relay /
Optical relay
Mode
Off –
Permanently off
On –
Permanently energised