TP Software User Manual
www.ismacontrolli.com
DMP253en | 1st Issue rev. 0 | 04/2022
page 37 of 49
Modbus
Address
Decimal
Address
Hex
Register Name
Access
Default
Value
Value
Range
Description
30301
300
0x12
C
TEMPERATURE_SEN
SOR
Read-
only
Actual temperature
sensor value with offset
30302
301
0x12
D
HUMIDITY_SENSOR
Read-
only
Actual humidity sensor
value with offset
30303
302
0x12
E
CO2_SENSOR
Read-
only
Actual CO2 sensor value
with offset
40304
303
0x12
F
TEMPERATURE_SEN
SOR_OFFSET
Read/
write
0
Temperature sensor
offset
40305
304
0x13
0
HUMIDITY_SENSOR
_OFFSET
Read/
write
0
Humidity sensor offset
40306
305
0x13
1
CO2_SENSOR_OFFS
ET
Read/
write
0
CO2 sensor offset
40307
306
0x13
2
TEMPERATURE_FILT
ER
Read/
write
60
Filtering time for the
temperature sensor
(seconds)
40308
307
0x13
3
HUMIDITY_FILTER
Read/
write
60
Filtering time for the
humidity sensor
(seconds)
40309
308
0x13
4
CO2_FILTER
Read/
write
60
Filtering time for the
CO2 sensor (seconds)
40316
315
0x13
B
TEMPERATURE_CO
NFIGURATION
Read/
write
17
Bit
Name
0
1
0
ACTIVE
Not active
Active
(def)
Activates/deactivates the
sensor
4
THIRD_POINT-
ACTIVE
No decimal
Decimal
(def)
Sets decimal places
40317
316
0x13
C
HUMIDITY_CONFIG
URATION
Read/
write
17
Bit
Name
0
1
0
ACTIVE
Not active
Active
(def)
Activates/deactivates the
sensor
4
THIRD_POINT-
ACTIVE
No decimal
Decimal
(def)
Sets decimal places
40318
317
0x13
D
CO2_CONFIGURATI
ON
Read/
write
1