TP Software User Manual
www.ismacontrolli.com
DMP253en | 1st Issue rev. 0 | 04/2022
page 42 of 49
BACnet
Type & ID
BACnet
Property
Decimal
Address
Hex
Object
Name
Access
Default
Value
Value
Range
Description
MSI1
Present
Value
28
0x1C
SENSORS
Read-
only
Informs
about built-in
sensors
AI1
Present
Value
200
0xC8
BACKLIGHT_LC
D
Read-
only
Actual display
illumination
value
AI2
Present
Value
201
0xC9
BACKLIGHT_KE
YPAD
Read-
only
Actual keypad
illumination
value
204
0xCC
DEVICE_CONFI
GURATION
Read/
write
BO0
Present
Value
BUZZER_ACTIV
E
1
Activates (1)
or deactivates
(0) a buzzer
BO3
Present
Value
LCD_BACKLIG
HT_ACTIVE
1
Switches the
LCD
background
illumination
on (1)
BO4
Present
Value
KEYPAD_BACK
LIGHT_ACTIVE
1
Switches the
keypad
background
illumination
on (1)
BO5
Present
Value
CO2_ALARM_L
CD
Switches on
the function
of LCD
background
illumination
flashing when
CO2 alarm
occurs
BO6
Present
Value
CO2_ALARM_B
UZZER
Switches on a
buzzer when
the CO2
alarm occurs
BO63
Present
Value
CO2_ALARM_C
ONFIRM
1
Allows to
enable
confirmation
of the CO2
alarm with
any button of
the panel